Generac Power Systems G0071450 Скачать руководство пользователя страница 30

Operation

24

Owner’s Manual for 50 Hz Air-Cooled Generator Sets

Automatic Transfer Operation

Proceed as follows to select automatic operation:

1.

Verify generator set is not running.

2.

Verify normal mains power source voltage is avail-
able to loads connected after transfer switch.

3.

Press AUTO button on control panel.

4.

Verify generator set MLCB (generator set discon-
nect) is set to ON (CLOSED).

The generator set will start automatically when mains
power source voltage drops below a preset level. Loads
are transferred to standby power source after unit starts.

Automatic Sequence of Operation

Mains (Utility) Power Failure

If the generator set is set to AUTO, when mains power
fails (below 156 volts), a five second line interrupt delay
timer is started (voltage and delay timer are dealer pro-
grammable). The engine cranks and starts if mains
power is still gone when the timer expires. An engine
warmup timer will be initiated once started. Timer dura-
tion varies depending on whether or not Cold Smart Start
is enabled. The controller will transfer the load to the gen-
erator set when the warmup time expires. If mains power
is restored (above 190 volts, dealer programmable) at
any time from the initiation of the engine start until the
generator set is ready to accept load (warmup time has
not elapsed), the controller completes the start cycle and
runs the generator set through its normal cooldown cycle.
However, the load will remain on the mains power
source.

Cranking

The system will go through five cyclic cranking cycles as
follows: 16 seconds cranking, 7 seconds resting, 16 sec-
onds cranking, 7 seconds resting, followed by three addi-
tional cycles of 7 seconds cranking followed by 7
seconds resting. An alarm will be triggered if the genera-
tor set does not start after five attempts.

Cold Smart Start

The Cold Smart Start feature is enabled at the factory, but
can be disabled in the EDIT menu. The generator set will
monitor ambient temperature when Cold Smart Start is
enabled. The warmup delay will be adjusted based on
prevailing conditions. 
If the ambient temperature is below a fixed temperature
(based on model) upon startup in AUTO mode, the gen-
erator set will warm up for 30 seconds before a load is
applied. The generator set will start with the normal war-
mup delay of five seconds if the ambient temperature is
at or above the fixed temperature.
A check for proper output voltage buildup is performed
when the generator set engine is started. 

Cleaning Cycle

If some condition impedes normal voltage creation, such
as frost crystals or dust/dirt preventing a good electrical
connection, the start sequence will be interrupted for a
cleaning cycle of the internal electrical connections. 
Cleaning cycle is an extended warmup period which lasts
for several minutes as normal generator set voltage out-
put is determined to be low. During this cycle, generator
set controller will display “Warming Up”.
Generator set controller display will show “Under Volt-
age” if the cleaning cycle fails to clear the obstruction.
After several minutes, the alarm message can be cleared
and the generator set restarted.
Make no further attempts to start if problem persists.
Contact an IASD.

Load Transfer

Load transfer priorities when the generator set is running
depend upon the transfer switch design. See transfer
switch owner’s manual.

Shutting Generator Set Down While 

Under Load Or During A Mains Power 

Outage

IMPORTANT NOTE: To avoid equipment damage,
follow these steps, in order, during mains power out-
ages. Shutdowns may be required during mains
power outages to perform routine maintenance or to
conserve fuel.

To turn generator OFF:

1.

Turn off mains power supply to transfer switch
using means provided (such as a mains MLCB).

2.

Set main circuit breaker in distribution panel to
OFF (OPEN) to remove all loads from generator
set.

3.

To shut down generator set:
– Allow generator set to run for five minutes at no

load.

– After five minutes, use emergency stop button to

shut down generator set.

– Wait 15 minutes to allow internal temperature to

stabilize.

NOTE: 

Failure to follow this procedure may expose user

to hot surfaces. See 

Hot Surfaces

 in Section 1.

ISO000191a

Automatic start-up. Disconnect mains 
power and render the equipment 
inoperable before attempting repairs or 
maintenance.

Содержание G0071450

Страница 1: ...r Sets 8 kVA to 13 kVA SAVE THIS MANUAL FOR FUTURE REFERENCE Register your Generac product at www activategen com 1 262 953 5155 ISO000209b This product is not intended to be used in a critical life s...

Страница 2: ...oblems and keeps operating expenses at a minimum It is the operator s responsibility to perform all safety inspections to verify all maintenance for safe operation is performed promptly and to have th...

Страница 3: ...Outdoor Noise Emission Directive 2000 14 EC ISO 8528 10 1998 Reciprocating internal combustion engine driven alternating current generating sets EN ISO 3744 2010 Determination of sound power levels a...

Страница 4: ...iv Owner s Manual for 50 Hz Air Cooled Generator Sets...

Страница 5: ...xercise 23 Manual Transfer Operation 23 Transfer to Generator Set Power Source 23 Transfer to Mains Power Source 23 Automatic Transfer Operation 24 Automatic Sequence of Operation 24 Mains Utility Pow...

Страница 6: ...Table of Contents vi Owner s Manual for 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 7: ...s manual contains important instructions that must be fol lowed during placement operation and maintenance of the unit and its components Always supply this manual to any individual that will use this...

Страница 8: ...negative battery cable D Fuel Selection Step 1 Unit set for Natural Gas NG operation Step 2 Press and rotate fuel selector 180 to change fuel type Step 3 Unit set for Liquid Propane LPG operation NOT...

Страница 9: ...l completely before installing or operating this equipment Do not smoke near this equipment Do not allow open flames near this equipment J Read Owner s Manual Read the manual for an explanation of thi...

Страница 10: ...Safety Information 4 Owner s Manual for 50 Hz Air Cooled Generator Sets Figure 1 1 Safety Decals A B C E F H J K G D L E M2 M1 P N Q K K 005771...

Страница 11: ...nstalled in accordance with the manufacturer s instructions and recommendations Following proper installation do nothing that might alter a safe installation and render the unit in noncompliance with...

Страница 12: ...properly grounded before applying power ISO000218 Installation must comply with all national and local electrical building codes ISO000147 Unit must be positioned in a manner that prevents combustible...

Страница 13: ...mospheres ISO000111 Keep clothing hair and appendages away from moving parts ISO000247a This unit is not intended for use as a prime power source It is intended for use as an intermediate power supply...

Страница 14: ...Always recycle batteries at an official recycling center in accordance with all local laws and regulations ISO000548 Batteries emit explosive gases while charging Keep fire and spark away ISO000162 Do...

Страница 15: ...et shutdown procedure in Shut ting Generator Set Down While Under Load Or During A Mains Power Outage before opening the enclosure This allows adequate cooling to reduce the risk of exposure to hot su...

Страница 16: ...Safety Information 10 Owner s Manual for 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 17: ...h cover F Oil drain K Status LED indicators O Sediment trap B Main line circuit breaker generator set disconnect G Composite base L Oil filter P Fuel regulator C Airbox with air cleaner H Exhaust encl...

Страница 18: ...0 Insulation Class 11 Power Factor 12 Controller Part Number 13 Country of Origin 14 Generator Duty Rating 15 Rated Ambient Temperature 16 Unbalanced Load Capacity 17 CE Conformity Marking 18 Generato...

Страница 19: ...76 dB A 77 dB A Sound pressure measurement uncertainty 1 dB A A Weighted sound power level LwA 94 dB A 94 dB A 95 dB A Sound power measurement uncertainty 1 dB A Normal operating range This unit is te...

Страница 20: ...tified to United States EPA emission standards or any other emission standards Sale or use of this generator set is not legal in the U S or any country which has emission standards applicable to this...

Страница 21: ...te procedures and details Battery Requirements 12 volts Group 26R 540CCA minimum or Group 35AGM 650CCA minimum not included with unit See Maintenance for correct battery maintenance proce dures Batter...

Страница 22: ...s necessary to perform complete routine maintenance on the generator set along with oil recommendations oil not included Fascia Base Wrap The fascia base wrap snaps together around the bottom of the n...

Страница 23: ...oof run off rain gutter down spouts and sump pump discharges are directed away from the generator set enclosure Generator Set Enclosure Opening the Lid Two locks secure the lid one on each side A in F...

Страница 24: ...ht of the control panel Verify both the left and right side locks are securely out of the way before closing the unit Figure 3 4 Generator Set Control Panel All appropriate panels must be in place dur...

Страница 25: ...warnings only the first message will be displayed Press the OFF mode button and then press the ENTER button to clear an alarm or warning Display Backlight Normally off The backlight will automatically...

Страница 26: ...unning Warning Warning Message Warning Message s Low Battery Exercise Set Error Service Schedule A Service Schedule B Inspect Battery Stopping FIRMWARE ERROR 9 Fuel Pressure Battery Problem Charger Wa...

Страница 27: ...XX XXXXX XX XX XX XX XX XX XXXXX NOTE 1 Last 50 logs displayed for each Alarm Log Run Log Maint Log NOTE 2 Date and time displayed for each occurence NOTE 3 Error code displayed for each Alarm Error...

Страница 28: ...ly safeguard during maintenance or service opera tions Follow the appropriate procedures in this manual to correctly disable the generator set during maintenance and service operations This device is...

Страница 29: ...d as follows to manually transfer to mains power and shut down generator set 1 Set main circuit breaker in distribution panel to OFF OPEN to remove all loads from generator set 2 To shut down generato...

Страница 30: ...conditions If the ambient temperature is below a fixed temperature based on model upon startup in AUTO mode the gen erator set will warm up for 30 seconds before a load is applied The generator set w...

Страница 31: ...l panel 2 Verify generator set MLCB generator set discon nect is OFF OPEN 3 Press AUTO button on the control panel 4 Generator set will start and run Allow generator set to run and warm up for a few m...

Страница 32: ...Operation 26 Owner s Manual for 50 Hz Air Cooled Generator Sets This page intentionally left blank...

Страница 33: ...s Power Outage 1 Turn on mains power supply to transfer switch using means provided such as a mains MLCB 2 Install 7 5A fuse in control panel 3 Press AUTO button on control panel 4 Set generator set M...

Страница 34: ...rvice Schedule for correct generator set operation Engine oil and oil filter must be changed and valve clear ance adjusted after the first 25 hours of operation Emissions critical maintenance must be...

Страница 35: ...lugs Inspect adjust valve clearance Inspect clean sediment trap See local codes and guidelines Contact the nearest IASD for assistance if necessary Remove any shrubs or tall grasses which have grown w...

Страница 36: ...r set back ON in Generator Set Enable Disable Proce dure Engine Oil Requirements Engine oil should be serviced in accordance with the rec ommendations of this manual to maintain product war ranty Main...

Страница 37: ...e Wait five minutes 13 Check oil level Add oil as needed DO NOT OVERFILL 14 Insert oil dipstick and or attach oil fill cap 15 Press AUTO button on the controller to return unit to AUTO mode 16 Close a...

Страница 38: ...ews attaching one valve cover using a 10 mm socket wrench Remove and dis card gasket 7 Verify piston is at top dead center TDC of its com pression stroke both valves closed To move pis ton to TDC remo...

Страница 39: ...n rocker arm jam nut Tighten jam nut to 11 After tightening jam nut verify valve clearance did not change 12 Install new valve cover gasket 13 Install valve cover Tighten fasteners in a cross pat tern...

Страница 40: ...isconnecting Battery Charger Cable 4 See Figure 4 8 Inspect battery posts and cables for tightness and corrosion Tighten and clean as necessary Figure 4 8 Battery Cables 5 Unsealed batteries only Comp...

Страница 41: ...a soft cloth Fre quent washing is recommended in salt water coastal areas Spray engine linkages with a light oil such as WD 40 Remove From and Return To Service Remove From Service If unit cannot be e...

Страница 42: ...tery is completely discharged or has been disconnected Decommissioning The generator set owner is responsible for correct decommissioning and disposal of this equipment when it has reached the end of...

Страница 43: ...Faulty spark plug s Clean inspect spark plug gap replace spark plug s as needed Valve clearance out of adjustment Reset valve clearance Engine starts hard and runs rough Air cleaner plugged or damage...

Страница 44: ...n IASD for assistance Faulty transfer relay Transfer relay circuit open Faulty control logic board Engine may be warming up See Cold Smart Start Check controller screen to verify status Unit consumes...

Страница 45: ...he startup delay is greater than expected contact an IASD to adjust from 2 to 1500 seconds LOW OIL PRESSURE RED Unit will not start in AUTO with mains power loss Check LEDs screen for alarms Check oil...

Страница 46: ...displays CHECK BATTERY replace the battery BATTERY PROBLEM YELLOW Yellow LED illuminated in any state Check screen for additional information Contact an IASD CHARGER WARNING YELLOW Yellow LED illumina...

Страница 47: ......

Страница 48: ...nc All rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S4...

Отзывы: