General Information
14
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
Engine
A detailed specification sheet for your particular generator set is available from an IASD or at
www.generac.com
.
Protection Systems
The generator set may need to run for long periods of
time with no operator present to monitor the engine/gen-
erator conditions. The generator set is equipped with pro-
tection systems to automatically shut down the unit to
protect against potentially damaging conditions. Some of
these systems include:
Alarms
:
Warnings:
The control panel contains a display which alerts the
operator when a fault condition occurs. The above list is
not all inclusive. See
about alarms and control panel operation.
NOTE:
A warning will indicate a condition on the genera-
tor set which should be addressed, but will not shut the
generator set down. An alarm will shut the generator set
down to protect the system from any damage. In the
event of an alarm, an owner can clear the alarm and
restart the generator set prior to contacting an IASD. If
the intermittent issue occurs again, contact an IASD.
Emission Information
The engine used in this generator set is not certified to
United States EPA emission standards, or any other
emission standards. Sale or use of this generator set is
not legal in the U.S or any country which has emission
standards applicable to this product.
Model
8 kVA
10 kVA / 13 kVA
Engine model
G-Force 500 Series
G-Force 1000 Series
Number of cylinders
2
2
Displacement
530 cc
999 cc
Cylinder block
Aluminum w/ cast iron sleeve
Recommended spark plug
Spark plug gap
0.76 mm (0.030 in)
1.02 mm (0.040 in)
Valve clearance
0.05–0.1 mm (0.002–0.004 in)
0.05–0.1 mm (0.002–0.004 in)
Starter
12 VDC
Oil capacity including filter
Approx. 1.6 L (1.7 qt)
Approx. 1.8 L (1.9 qt)
Oil consumption
Approx. 5-10 mL per hour (0.17–0.34 oz. per hour) at an average load of 50%
Recommended oil filter
Recommended air filter
Engine power is subject to and limited by such factors as fuel joules/BTU, ambient temperature and altitude. Engine power
decreases approximately 3.5% for each 304.8 m (1,000 ft) above sea level, and also will decrease approximately 1% for each 6 °C
(10 °F) above 15 °C (60 °F) ambient temperature.
•
High Temperature
•
Low Oil Pressure
•
Overcrank
•
Overspeed
•
Overvoltage
•
Undervoltage
•
Overload
•
Underspeed
•
RPM Sensor Loss
•
Controller Fault
•
Wiring Error
•
Stepper Overcurrent
•
Emergency Stop
•
Charger Warning
•
Charger Missing AC
•
Low Battery
•
Battery Problem
•
Exercise Set Error
•
USB Warning
•
Download Failure