![Generac Power Systems G0071450 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/generac-power-systems/g0071450/g0071450_owners-manual_2209512019.webp)
General Information
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
13
Specifications
Generator Set
Model
8 kVA
10 kVA
13 kVA
Rated voltage
220
Alternate voltage
230/240
Rated maximum load
current (amps) at rated
voltage*
36.4
45.5
59.1
Maximum load current
(amps) at alternate
voltage*
34.8 / 33.3
43.5 / 41.7
56.5 / 54.2
Main line circuit breaker
40 A
50 A
63 A
Phase
1
Rated AC frequency
50 Hz
Battery requirement
Group 26R, 12 Volts and 540 CCA Minimum (See
)
Enclosure
Aluminum
Weight (kg / lb)
154.7 / 341
176.4 / 389
192.8 / 425
A-Weighted sound
pressure level (LpA)
75 dB(A)
76 dB(A)
77 dB(A)
Sound pressure
measurement uncertainty
1 dB(A)
A-Weighted sound power
level (LwA)
94 dB(A)
94 dB(A)
95 dB(A)
Sound power
measurement uncertainty
1 dB(A)
Normal operating range
This unit is tested in accordance to ISO 8528 standards with an operating temperature of -29 °C
(20 °F) to 50 °C (122 °F). For areas where temperatures fall below 0 °C (32 °F) a cold weather kit is
recommended. When operated above 25 °C (77 °F) there may be a decrease in engine power. Please
reference the engine specifications section.
These generator sets are rated in accordance with ISO 8528, Reciprocating Internal Combustion Engine Driven Alternating Current
Generating Sets–Safety.
* Natural gas ratings will depend on specific fuel joules / BTU content. Typical derates are between 10-20% off the LP gas rating.