Operation
Owner’s Manual for 50 Hz Air-Cooled Generator Sets
17
Section 3: Operation
Site Prep Verification
The generator set must be installed so airflow into and out
of the generator set is not impeded.
Mechanical and gravity outdoor intake openings for air
distribution and supply systems shall be located not less
than 3048 mm (10 ft) horizontally from the generator set
enclosure. See Section 401.4 in the ICC Mechanical
Code for additional information.
Verify all shrubs or tall grasses within 0.91 m (3 ft) of the
intake and discharge louvers on the sides of the enclo-
sure have been removed, and no other walls or objects
are within 0.91 m (3 ft) of the louvers. Install the genera-
tor set on high ground where water levels will not rise and
endanger it. This unit should not operate in or be sub-
jected to standing water. Verify all potential water sources
such as water sprinklers, roof run-off, rain gutter down-
spouts, and sump pump discharges are directed away
from the generator set enclosure.
Generator Set Enclosure
Opening the Lid
Two locks secure the lid—one on each side (A in
). Open the protective rubber cap to access the key-
hole, and press down on the lid above the side lock and
unlock the latch to properly open the lid.
Figure 3-1. Side Lock Location
Repeat for the other side. The lid may appear stuck if
pressure is not applied from the top.
Always verify side locks are unlocked before attempting
to lift the lid.
NOTE:
Two identical sets of keys were provided with the
generator set as shipped from the factory. Keys are
intended for service personnel use only. Contact installer
if keys cannot be located.
Generator Set Main Line Circuit
Breaker (Generator Set Disconnect)
This is a 2-pole main line circuit breaker (MLCB) (genera-
tor set disconnect) rated according to relevant specifica-
tions. See “A” in
.
Indicator (B) Identifier—Green means OFF (OPEN). Red
means ON (CLOSED).
Figure 3-2. Generator Set Main Line Circuit Breaker
005623
A
A
006640
A
B