23
6\VWHP 7URXEOHV
Use the System Trouble chart on the following
page to determine the specific System Trou-
ble(s).
During normal panel operation the
SYSTEM
TROUBLE LED has the following two modes of
operation:
STEADY
1-7 possible trouble
groups, AC is present
FLASHING
1-7 possible trouble
groups, AC is not
present
9LHZLQJ 6\VWHP 7URXEOHV
Press the
key on the keypad.
To determine the System Trouble Group Num-
ber, count the number of times the
SYSTEM
TROUBLE LED blinks. The keypad sounder will
beep at the same rate that the
SYSTEM
TROUBLE LED blinks.
To determine the System Trouble, note the zone
LED that is ON. Look up the specific system
trouble on the chart on the following page.
The
SYSTEM TROUBLE LED and keypad
sounder will continue to flash and beep. To view
the next System Trouble, if any, press the
key. Continue pressing the
key, if there are
no more system troubles to view, the system will
return to normal operation.
Note: System Troubles Groups 3 through 7 -
System Trouble Groups that have a zone or
smoke detector associated with the trouble,
such as RF low battery. The zone(s) of the
device with a low battery will be displayed by
the ZONE LED . For example, a wireless low
battery on zone 2 would beep the keypad
sounder 3 times and turn on zone 2 LED.
Audible System Trouble Indication - For all
system troubles, except when the only system
trouble is the loss of AC, the keypad will beep
once every 10 seconds. The keypad will continue
to beep until the reset button is pressed or the
trouble has been acknowledged by pressing the
key.
System Trouble Reporting
The following system troubles, when enabled to
report to Telco 1 [37-3] or Telco 3 [57-3], will send
the report code programmed in Trouble Report
[63] if reporting using a pulse format:
System Trouble
Pulse Report Code
Bell Cut
F1
2-Wire Fire Trouble
F1
Rcvr Fail-to-Respond
F1
Receiver Tamper
F1
Receiver JAM
F1
Tx Low Battery
F1
Tx Supervisory Failure
F1
Smoke Low Battery
F1
Smoke Sup. Failure
F1
If reporting using Point ID, a unique code will be
sent for each of the following System Troubles.
System Trouble
Point ID Report Codes
Bell Cut
CODE 1 321 G00 ZN000-BELL 1 TROUBLE
2-Wire Fire Trouble
CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
Rcvr Fail-to-Respond
CODE 1 382 G00 ZN000-SENSOR TROUBLE
Receiver Tamper
CODE 1 145 G00 ZN000-EXP. MODL. TAMPER
Receiver JAM
CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
Tx Low Battery
CODE 1 384 G00 ZN00n-RF TRAN LOW BATT
Tx Supervisory Failure
CODE 1 381 G00 ZN00n-SUPERVSN LOSS RF
*Smoke Low Battery
CODE 1 384 G00 ZN00n-RF TRAN LOW BATT
*Smoke Sup. Failure
CODE 1 381 G00 ZN00n-SUPERVSN LOSS RF
*Smoke Detectors 1 - 4 report as ZN009 - ZN012
A 300 (SYSTEM TROUBLE RST) code is sent if a restore is
reported after multiple troubles.
System Trouble
Group #
Keypad SYSTEM Trouble
LED is flashing 1 time indicat-
ing System Trouble Group 1.
Keypad Sounder beeps 1
time indicating System Trou-
ble Group 1.
EXAMPLE
-
LOW BATTERY SYSTEM TROUBLE DISPLAY
Zone LED(s)
is ON
indicates
(Specific Trouble)
Specific Trouble
Zone 2 LED is ON indicating
Low Battery. (1 Beep, LED 2)
Flashing
(System Trouble
Group Number)
Enter
to enter System Trouble mode
and determine the specific trouble. Press any key to
view all system troubles.
ARM
ED
G E M I N I
2
STA
TUS
Beeping
(System Trouble
Group Number)
FIGURE
9 S
YSTEM
T
ROUBLE
E
XAMPLE
Wi850a
page 23
Tuesday, September 16, 1997 08:01