13
cally be unbypassed and any subsequent
violations of the zone will cause an alarm
condition.
[04]24-Hour Protection
A zone that provides protection at all times,
whether or not the system is armed.
[05]40 ms Loop Response
Normally loop response is 750 ms, select
this option to change the loop response to 40
ms. The slower the loop response, the less
sensitive the system will be to intermittents
(swingers). The programming option is not
permitted for UL installations.
[06]Open Circuit Zones
Program this zone type if unsupervised nor-
mally open circuit devices are required The
programming option is not permitted for UL
installations.
[07]Burg (Steady) Output
Enables the Bell Output on a zone trip for
each zone selected. The Bell Output will
remain ON for the length of time pro-
grammed for
Burg (Steady) Output [07] or it
will remain ON until turned off by entering a
valid Arm/Disarm Code; 0 means output
will stay ON until reset.
[08]PGM Output
Enables the PGM Output on a zone trip for
each zone selected. The PGM Output will
remain ON until reset.
[09]Selective Bypass
Enables the ability of the User to bypass
zones. By default, all zones are permitted
to be bypassed.
6\VWHP 7LPHV
[10]Exit Delay
The delay time which permits exit through
an
Exit/Entry Zone [00] after the system is
armed, allows a user to leave the premises
without
setting off an immediate alarm.
Exit Delay may be programmed for up to
255 seconds (4¼ minutes); a value of 0
defaults to 60 seconds.
[11]Entry Delay
Delay time permits entry through
Exit/Entry
Zone(s) after the system is armed without
setting off an immediate alarm.
Entry Delay
allows the user time to enter and disarm the
system. Upon entering, the keypad sounder
will sound a steady tone (Entry Sound) to
remind the user to disarm the system.
Entry
Delay Time [11] may be programmed for up
to 255 seconds (4¼ minutes); a value of 0
defaults to 30 seconds.
Entry Delay may be
canceled by pressing
before or after
arming.
[12]Burg (Steady) Output Time-out
Can be programmed from 1 to 255 min (4¼
hours); 0 means output will stay ON until
turned off by entering an Arm/Disarm Code.
[13]Fire (Pulsed) Output Time-out
Can be programmed from 1 to 255 min (4¼
hours); 0 means output will stay ON until
turned off by entering an Arm/Disarm Code.
[14]Test Timer Interval
Program the interval, in days, between Test
Timer reports. Test Timer Interval may be
programmed from 1 to 255 days.
Normally Open Zone Wiring
Wire the normally
open contact
as shown (Zone 4).
EZ Zone Doubling
TM
resistor
is required.
Program the
zone for
Open Circuit [06].
.
(Z)
ZONE 1
(E)
.
ZONE 4
FIGURE
6 O
PEN
C
IRCUIT
W
IRIING
Wi850a
page 13