5. Enter Standby Mode by entering
R
.
The Computer is now in STANDBY
Site
At the site perform the following three steps:
1. Arm the panel.
2. Disarm the panel.
3. Enter
. The panel will now
call the download computer running
PCPreset. PCPreset will answer the
call, establish a connection, and then
download the account that matches the
Auto Download ID Number [93] with the
account of the same number in the list
that PCPreset is currently running.
'HDOHU 3URJUDPPLQJ
[94]Dealer Code
The default Dealer Code is
4567
. Program
a new 4-digit Dealer Code. When the panel
is defaulted the Dealer Code will be changed
back to the default Dealer Code of
4567
only
if Dealer Code Lockout [96-1] has not
been programmed.
[95]User 1 Code
The 1st User code is a program code as
well as an Arm/Disarm code. The default
User Code is
1234
. If User 1 Code Lock-
out is programmed the User 1 Code cannot
be programmed from User Program Mode.
[96]Dealer Options 1
(1) Dealer Code Lockout - Program to
prevent the Dealer Code from changing
with a panel default.
(2) User 1 Code Lockout - If programmed
the User 1 Code cannot be programmed
from User Program Mode.
(3) Household Fire - Activates the follow-
ing UL required features:
There is a 4 hour re-sound of wireless
Smoke Low Battery and wireless Smoke
Supervisory system troubles.
•
An active System Battery test per-
formed every 4 hours instead of 24
hours and Wireless Smoke Supervisory
Timer is set to 4 hours.
•
Fire Bell Timing is March Time.
•
Wireless Smoke Supervisory Time is
fixed at 4 hours.
(4) Fire Trouble on Fire LED - Normally
all troubles are displayed on the
SYS-
TEM TROUBLE LED, including Fire Trou-
ble. If required Fire Trouble can be dis-
played on the Fire LED. Fire Trouble is
indicated by a steady
Fire LED.
[97]Dealer Options 2
(1) International Dialing Protocol - No dial-
ing if no dial tone, 60 s between attempts
and 4 s wait for dial tone.
(2) Invert Bell Output - Inverts the Bell
polarity and removes supervision from the
bell circuit.
(3) System Trouble Auto Restore - Nor-
mally, System troubles require acknowledg-
ment (View System Trouble) in order to re-
store. If this option is selected troubles will
restore without requiring acknowledgment.
(4) User 1 Code-Program only - If enabled
User 1 Code will function only as the User
Program Code and will not Arm/Disarm the
panel.
Note: All programming within Programming
Blocks [96] & [97] will not
change if the panel
is defaulted.
[98] Number of Re-Dials
The Number of re-dial attempts made by the
panel before indicating a
Fail-to-
Communicate
(System Trouble 1-3).
Wi850a
page 22
Tuesday, September 16, 1997 08:01