21
are pressed when the system is armed with
Exit/Entry Follower Zones or Home/Away
with Delay Zones that have been bypassed.
8 Interior
Program an 8 in the AUX 1 and/or AUX 2
option to Bypass Exit/Entry Follower Zones
or Home/Away with Delay Zones when the
or
buttons on the Keyfob are
pressed (only if the system is programmed
exclusively for
Home/Away with Delay
Zones).
[85] - [88] Wireless Smoke Detectors
Enter the RF ID# of the smoke detector.
A wireless smoke detector sends a supervi-
sory transmission about once every hour. If
the receiver does not receive a signal from a
transmitter in the time programmed in Wire-
less Smoke Supervisory Timer, a system
trouble ‘RF Smoke Supervisory Failure' will
be indicated on the keypad.
Program Wireless Smoke Supervisory Timer
[17] to change the time from the default time
of 8 hours. Refer to Household Fire [96-3].
Note: Mark Smoke Detectors (Smoke 1
through Smoke 4) in order to identify them in
the event of a supervisory or battery failure.
If
Household Fire [96-4] is selected, Wireless
Smoke Supervisory Time is fixed at 4 hours.
'RZQORDGLQJ
[90]Callback Telephone Number
Program the phone number of the down-
loading computer to be dialed by the panel
during a high security download.
[91]Ring Count
Program the number of rings before the
panel will pickup.
Ring Method [92-1]
(Downloading Features) must also be se-
lected.
[92]Downloading Features
(1) Ring Method - Enable the ring method
of downloading. The panel will pick-up on
the number of rings programmed in
Ring
Count [91].
(2) Answering Machine Override - Using
the downloading computer, call the panel.
When the operator has determined that the
panel has received 1-2 rings, pressing the
X
key will cause the downloading com-
puter to immediately re-dial the panel. The
panel will pick-up on the first ring.
(3) Function 6 Download - Select to en-
able the
method of downloading
(pg. 8).
(4) Signal Strength Test Mode - Program
to initiate a 2 hour test period. The signal
strength information for all supervisory sig-
nals received over a two hour period will be
saved to the LOG.
[93]Auto Download ID Number
Enter the Number that is used by PCPreset
when downloading using Site Initiated Auto
Downloading (
).
The requirements for Site Initiated Auto
Downloading are as follows:
1. Download Computer running PCPreset.
2. Program the telephone number of the
Download Computer in location [90]
Call-
back Telephone Number.
3. Program location [93] with the number of
the PCPreset account that is to be down-
loaded.
PCPreset
1. Create the GEM-P800 account to be
downloaded using PCD3000 Quick-
loader Software.
2. Create a List using PCPreset.
3. Select the account by pressing
WW
.
Select the desired account from the list
of PCD3000 accounts available. (The
location in the list is the
Auto Download
ID Number [93])
4. Tag the list by entering
D'
(
download)
Wi850a
page 21