GFK-1504N
Chapter 14 Temperature Sensing Modules
14-7
14
IC200ALG620
Analog Input, 16 Bit RTD, 4 Channels
Configurable Parameters
The default parameters of the RTD Input module can be used in many
applications. The module can be software-configured when it is installed in a
VersaMax PLC system or an I/O Station controlled by a NIU that is version 2.0
or above.
Module
Parameter
Description
Default
Choices
Analog Input
Data Length
Word length of the module’s
analog input data.
4
0–4
Analog Input
Data
Reference
Starting offset for the
module’s analog input data.
user selectable
Line
Frequency
Specifies the line frequency.
60 Hz
50 Hz, 60 Hz
Channel
Active
Specifies if the channel
should return data and
alarms. If a channel is
“inactive” space is still
allocated for it.
Active
Inactive (off), Active (on)
Units
The conversion type for each
RTD.
Deg C
tenths of
Ω, tenths of °C, or tenths of °
F
RTD Type
The type of RTD used for
each channel.
100 PT 385
10 PT, 25 PT, 25.5 PT 392, 100 PT 385, 100
PT 3902, 100 PT 392, 100 PT 3923, 100 PT
3916, 1K PT 375, 10 CU, 10 CU 427, 50 CU
427, 100 CU 427, 100 NI, 100 NI 618, 120 NI
672 604 NI/FE 518, 1K NI/FE 527, 500 Ohm,
3000 Ohm
Wire Type
The type of field wiring for
each RTD.
3 Wire
3 Wire, 4 Wire
Alarm Low
The low alarm limit for the
channel, in engineering units.
–2000
–32,768 to +32,767
Alarm High
The high alarm limit for the
channel, in engineering units.
8000
–32,768 to +32,767
Nominal
Resistance
An optional resistance
adjustment, in tenths of
Ω.
0
0 to 3276.7
Channel
Default Input
Specifies analog input
returned upon error (including
open circuit errors).
0
+ 3276.7