11-24 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
11
IC200ALG325
Analog Output Module, 13 Bit Voltage 8 Channels
Jumper Selection
Jumpers on the carrier can be used to select the output range and output
default mode.
Range Jumper
If no jumper is installed on pins B1 and B2, outputs are configured for the
bipolar range of –10 to +10 V. With a jumper installed, the outputs are
configured for the unipolar range of 0 V to +10 V.
Range Jumper (JMP 1)
Range
None
-10 to +10 V
Installed
0 to +10 V
Hold Jumper
If no jumper is installed on pins B2 and B3, outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications
are interrupted or the PLC is stopped. With a jumper installed, outputs default
to 0 V. This should only be changed with the field power and backplane power
removed.
Hold Jumper (JMP 2)
Output Default
None
Hold Last State
Installed
0 V
Wiring Example
JMP 2
Jumper installed = unipolar range
no jumper = bipolar range
JMP 1
Field Power
Field Return
-
+
Load 1
Shield
V OUT 1
Return 1, 2
Load 2
V OUT 2
Shield
RET
Jumper installed = default to 0V
no jumper = hold last state