3-18
VersaMax Modules, Power Supplies and CarriersUser's Manual
GFK-1504N
3
IC200PWR202
12V DC Expanded 3.3 V Power Supply
Specifications
Input Voltage
9.6 to 15 V DC, 12V DC nominal
Input Power
11W
Holdup Time
10ms
Inrush Current
25 A at 12V DC
30A at 15 V DC
Output Voltage
5 V DC, 3.3 V DC
Protection
Short circuit, overload, reverse polarity
Output Current
Total
3.3 V DC Output
5 V DC Output
1.5 A maximum
†
1.0A maximum
(1.5 A - I
3.3 V
) maximum
†
The total output current should not exceed 1.5 A. For example, if 3.3 V
at 1.0A is required, 0.5A is available on the 5 V output.
Wiring
DC- must be grounded to frame / earth ground. DC- is grounded to frame
internally in the Power Supply. As a result, floating power supplies cannot
be used.
DC+
DC-
For agency compliance, external MOV suppression as detailed in chapter 2 is
required from both the positive and negative inputs to frame ground or at the
power line input of a system enclosure. MOV protection across the inputs is
provided on the supply and not necessary to add externally.