10-32 VersaMax Modules, Power Supplies and Carriers User's Manual
GFK-1504N
10
IC200ALG262
Analog Input Module, 14 Bit Differential Current 8 Channels
Jumper Selections
A jumper selects the current input range.
Jumper
Range
None
4-20mA
Installed from A18 to A17
0-20mA
Wiring Examples
Input 1 (-)
Input 1 (+)
Jumper
Field Return
Jumper
Wire
Terminal Connections
Current
Source
Current
Source
Input 8 (-)
Input 8 (+)
An external source must be provided to power input transceivers.
Cable Shield Connections
If possible, the cable should be grounded at the source device. If that is not
possible, the cable shield must be grounded at the source device. If that is not
possible, the cable shield must be grounded at the I/O module. This can be
done using an Auxiliary I/O Terminal (IC200TBM001, 002, or 005).
If the module is installed on a Terminal-style I/O Carrier (IC200CHS001, 002, or
005), shield connections can be made on an Auxiliary I/O Terminal that is
attached to the I/O carrier.
If the module is installed on a Compact Terminal-style I/O Carrier
(IC200CHS022, 025), shield connections can be made on an Auxiliary I/O
Terminal that is mounted near the I/O carrier. Be sure to ground the Auxiliary
I/O Terminal Strip if you plan to use it for this purpose.
If the module is installed on a Connector-style I/O Carrier (IC200CHS003), the
cable shield can be connected directly to an Interposing Terminal
(IC200CHS011, 012, 015). Be sure to ground the Interposing Terminal. It is
recommended to use a shielded interposing cable as well between the
Interposing Terminal and the Connector Base. A custom shielded cable can be
made using the Connector kit (IC200ACC304). In addition, a custom shield
braid can be wrapped around standard Interposing Cables (IC200CBL105, 110,
120, 230). If this approach is used be sure to ground the braid.