GFK-1504N
Chapter 11 Analog Output Modules
11-39
11
IC200ALG327
Analog Output Module, 13 Bit Voltage 12 Channels
Scaling for Unipolar Outputs
The following graph illustrates the relationship between the output voltage
measured at the field terminals and the data that is output by the module, when
outputs are set up for the
unipolar range.
Count vs Output Voltage, Unipolar
0 3200 6400 9600 12800 16000 19200 22400 25600 28800 32000
12
11
10
9
8
7
6
5
4
3
2
1
0
Count
Voltage
5.0075V
5.00875V
16032
16028
16024
16020
5.00625V
5.0100V
4 counts =
1.25mV
Voltage can be calculated using the following equation:
Vout = ( (analog counts x 10.24) / 32768 )
The count value must be a multiple of 4. If the module receives a count value
that is not a multiple of 4, it rounds the value down to the closest multiple of 4.
For example:
Count
Voltage
16024
5.0075V
16026
5.0075V
16028
5.00875V