2-16 VersaMax Modules, Power Supplies and CarriersUser Manual
GFK-1504N
2
Jumper Installation on an AC Power Supply Module
AC power supply modules (IC200PRW101 and IC200PWR102) can be used
with either 120 V AC or 240 V AC nominal input power. For 120 V AC nominal
operation, install a jumper as marked on the power supply. Use insulated AWG
#14 (avg. 2.1mm
2
cross section) to AWG #22 (avg. 0.36mm
2
cross section)
wire.
JUMPER
FOR 120V
The power supply operates without a jumper installed; however, the hold-up
specification is not met. If a jumper is not installed for 120 V AC operation, the
power supply will not cause hazardous conditions.
Warnings
DO NOT USE A JUMPER FOR 240V AC OPERATION. If a jumper is used on
the input connector for 240V AC nominal operation, the power supply will
be damaged and may cause hazardous conditions.
Do not touch the exposed portions of the jumper wire with power applied
to the system. Hazardous voltages are present that could cause personal
injury.