GFK-1504N
Chapter 10 Analog Input Modules
10-41
10
IC200ALG264, IC200ALG266: Analog Input Module, 15 Bit Current 15 Channels
Configuration Parameters
A jumper on the carrier terminals can be used to configure 4-20mA or 0-20mA
input ranges. With no jumper installed, the module accepts 4-20mA input
signals. With a jumper installed, the module accepts 0-20mA input signals.
The analog inputs are software-configurable to either default or hold last state
upon loss of module.
Module Specifications
Module Characteristics
Channels
15 single ended, one group
Module ID
FFFFB50F (when cfg for 4-20mA range)
FFFFB40F (when cfg for 0-20mA range)
Isolation:
User input to logic (optical) and
to frame ground
Group to group
Channel to channel
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
None
LED indicators
OK LED. See "LED Indicators" for description.
Backplane current consumption
IC200ALG264: 5V = 100mA maximum
IC200ALG266: 5V = 100mA, +3.3V = 50mA maximum
External power supply
None
Thermal derating
None
Configuration parameters
Range select (jumpers on carrier)
Diagnostics
Loss of Internal Power, Open wire detection of 4-20mA
signals only. Module IC200ALG266 only: A/D conversion
malfunction greater than 6% full scale.
Compatibility
PME programming
software
CPU
001
CPU
002
CPU
005
CPU
E05
DBI
001
EBI
001
GBI
001
PBI
001
HW, FW version
FW release
All
CE
2.1
AB
2.1
AA
2.1
AA
2.1
No
AB
1.1
BF
2.2
CF
2.2
Input Characteristics
Input current
4 to 20mA (default : no terminal jumper installed)
0 to 20mA (with terminal jumper installed)
Input Fault Withstand
IC200ALG264: +3V; IC200ALG266: +30V
Input Impedance
100
Ω
Accuracy at:
25 °C
†
0 to 60 °C
±0.3% typical of full scale, ±0.5% maximum of full scale
±1% maximum of full scale
Resolution
15 bits
0.5
µ
A = 1 counts (for 4-20mA range)
0.625
µ
A = 1 counts (for 0-20mA range)
Filter response (3dB Corner Freq)
24 Hz ±0%
Update rate per module
7.5ms
†
In the presence of severe RF interference, (IEC 1000-4-3, 10V/m), accuracy may be degraded
to ±2%.