5-210
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
IEC curves
For European applications, the relay offers three standard curves defined in IEC 255-4 and British standard BS142. These
are defined as IEC Curve A, IEC Curve B, and IEC Curve C. The IEC curves are derived by the operate and reset time
equations.
Eq. 5-33
where
T = operate time (in seconds)
TDM = Multiplier setting
I = input current
I
pickup
= Pickup Current setting
K, E = constants defined in the table
t
r
= characteristic constant defined in the table
T
RESET
= reset time in seconds (assuming energy capacity is 100% and
RESET
is “Timed”)
Table 5-29: IEC (BS) inverse time curve constants
Table 5-30: IEC curve trip times (in seconds)
IEC (BS) curve shape
K
E
t
r
IEC Curve A (BS142)
0.140
0.020
9.7
IEC Curve B (BS142)
13.500
1.000
43.2
IEC Curve C (BS142)
80.000
2.000
58.2
IEC Short Inverse
0.050
0.040
0.500
Multiplier
(TDM)
Current ( I / I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IEC Curve A
0.05
0.860
0.501
0.315
0.249
0.214
0.192
0.176
0.165
0.156
0.149
0.10
1.719
1.003
0.630
0.498
0.428
0.384
0.353
0.330
0.312
0.297
0.20
3.439
2.006
1.260
0.996
0.856
0.767
0.706
0.659
0.623
0.594
0.40
6.878
4.012
2.521
1.992
1.712
1.535
1.411
1.319
1.247
1.188
0.60
10.317
6.017
3.781
2.988
2.568
2.302
2.117
1.978
1.870
1.782
0.80
13.755
8.023
5.042
3.984
3.424
3.070
2.822
2.637
2.493
2.376
1.00
17.194
10.029
6.302
4.980
4.280
3.837
3.528
3.297
3.116
2.971
IEC Curve B
0.05
1.350
0.675
0.338
0.225
0.169
0.135
0.113
0.096
0.084
0.075
0.10
2.700
1.350
0.675
0.450
0.338
0.270
0.225
0.193
0.169
0.150
0.20
5.400
2.700
1.350
0.900
0.675
0.540
0.450
0.386
0.338
0.300
0.40
10.800
5.400
2.700
1.800
1.350
1.080
0.900
0.771
0.675
0.600
0.60
16.200
8.100
4.050
2.700
2.025
1.620
1.350
1.157
1.013
0.900
0.80
21.600
10.800
5.400
3.600
2.700
2.160
1.800
1.543
1.350
1.200
1.00
27.000
13.500
6.750
4.500
3.375
2.700
2.250
1.929
1.688
1.500
IEC Curve C
0.05
3.200
1.333
0.500
0.267
0.167
0.114
0.083
0.063
0.050
0.040
0.10
6.400
2.667
1.000
0.533
0.333
0.229
0.167
0.127
0.100
0.081
0.20
12.800
5.333
2.000
1.067
0.667
0.457
0.333
0.254
0.200
0.162
0.40
25.600
10.667
4.000
2.133
1.333
0.914
0.667
0.508
0.400
0.323
0.60
38.400
16.000
6.000
3.200
2.000
1.371
1.000
0.762
0.600
0.485
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...