5-160
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
The breaker control element contains the auxiliary logic for status and serves as the interface for opening and closing of a
circuit breaker from protection, autoreclose, SCADA, or through the front panel interface. The breaker control element can
be used to create interlocking functionality. For greater security in determination of the breaker position, both the 52/a and
52/b auxiliary contacts are used with reporting of the discrepancy between them.
To use this element, configure the contact outputs that trip and close the breaker to use FlexLogic operands
BREAKER 1 OFF
CMD
(or
BREAKER 1 TRIP A/B/C
in the case of single-pole tripping) and
BREAKER 1 ON CMD
, and configure the breaker control
element inputs as described here.
A description of the operation of the breaker control and status monitoring features from the front panel is provided in
chapter 4.
There are two breaker control elements for each CT/VT module installed. The following settings are available for each
breaker control element.
BREAKER 1 FUNCTION
— This setting enables and disables the operation of the breaker 1 control feature.
BREAKER1 PUSH BUTTON CONTROL
— Set to “Enable” to allow front panel pushbutton open/close control operations.
BREAKER1 TAGGING
— Set to "Enable" to allow the graphical front panel to tag breaker 1. When tagged, the following
operations are disabled: pushbutton open/close, IEC 61850 open/close, and close command initiated by
BREAKER 1 CLOSE
setting. The trip command issued by the Trip Out element or
BREAKER 1 OPEN
setting is not affected.
BREAKER1 SUBSTITUTN
— Set to "Enable" to allow the graphical front panel to substitute breaker 1 status. When substituted,
breaker 1 control open/close status is forced to the substituted value.
BREAKER1 BYPASS
— Set to "Enable" to allow the graphical front panel to bypass breaker 1 interlocking. When asserted,
BREAKER 1 BLK OPEN
and
BREAKER 1 BLK CLOSE
settings are bypassed.
BREAKER1
Φ
A/3P CLSD:
Off
Range: FlexLogic operand
BREAKER1
Φ
A/3P OPND:
Off
Range: FlexLogic operand
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic operand
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic operand
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic operand
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic operand
BREAKER 1 TOPERATE:
70 ms
Range: 0 to 65535 s in steps of 1
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic operand
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
BREAKER 1 OPEN
SEAL-IN: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic operand
BREAKER 1 RACKED-IN:
Off
Range: FlexLogic operand
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...