CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
7-5
7
CLEAR SECURITY DATA
— Selecting ‘Yes’ allows the Supervisor to forcefully clear all the security logs and clears all the
operands associated with the self-tests.
7.2 Targets menu
A target enables the EnerVista UR Setup software to monitor automatically and display the status of any active target
messages of all the devices inserted into that site.
Each T35 element with a TARGET setting has a target message that when activated by its element is displayed in sequence
with any other currently active target messages in the
TARGETS
menu. In the example shown, the Phase TOC4 and Digital
Element 48 target settings are active and so have their targets displayed. And the Digital Counter 1 and Digital Counter 16
target settings are active (and none between the two) and so have their targets displayed. The down arrow below the two
elements indicates that there can be other active elements beyond these two.
For more information, see the description of target messages in the next section, and the Introduction to Elements section
in the Settings chapter for instructions on TARGET setting.
When no targets are active, the display reads
NO ACTIVE TARGETS
.
7.2.1 Target messages
When there are no active targets, the first target to become active causes the display to immediately default to that
message. If there are active targets and the user is navigating through other messages, and when the default message
timer times out (i.e. the keypad has not been used for a determined period of time), the display again defaults back to the
target message.
The range of variables for the target messages is described below. Phase information is included if applicable. If a target
message status changes, the status with the highest priority displays.
Table 7-1: Target message priority status
If a self test error is detected, a message appears indicating the cause of the error. For example UNIT NOT PROGRAMMED
indicates that the minimal relay settings have not been programmed.
TARGETS
DIGITAL COUNTER 1:
LATCHED
Displayed only if targets for this element are active.
Example shown.
DIGITAL COUNTER 16:
LATCHED
Displayed only if targets for this element are active.
Example shown.
DIGITAL ELEMENT 48:
LATCHED
Displayed only if targets for this element are active.
Example shown.
Priority
Active status
Description
1
OP
element operated and still picked up
2
PKP
element picked up and timed out
3
LATCHED
element had operated but has dropped out
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...