CHAPTER 5: SETTINGS
PRODUCT SETUP
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
5-33
5
CURRENT PAGE
Range: Page 1...Page 5
Default: Page 1
Select the metering page to configure from the drop-down list. There are five pages possible, viewable with the Tab
pushbuttons on the graphical front panel.
PAGE NAME
Range: Page 1...Page 5
Default: Page 1
Up to 20 characters can be input here as the name of each metering page. The name displays for the Tab pushbutton on
the graphical front panel.
LAYOUT
Range: 3x4, 4x6, 6x8, 6x4, 8x6, 12x8, 12x4, 16x6, 18x8
Default: 12x4
This setting determines how many rows and columns display on the graphical front panel with the metering information.
The configurable rows in the settings window change dynamically based on this setting.
CONTENT
Range: Actual, Status, Text
Default: Text
Select the type of content to display. Actual refers to an actual value/data. Status refers to one of the operands selected
from the STATUS INPUTS fields. Text indicates that text is to display instead of a metered value.
A maximum of eight Status Inputs can be used per metering page, and 16 in all metering pages.
STATUS INDEX
Range: 1...16
Default:
This field becomes active when the
CONTENT
field is set to Status. It selects the input from the STATUS INPUTS to display
the on/off status of the selected operand.
TEXT
Range: up to 20 alphanumeric characters
Default:
Enter the text to display on the graphical front panel. This field is active when the
CONTENT
field is set to Text or Status.
When Status is selected, the text displays when the status input is in the "on" state.
OFF TEXT
Range: up to 20 alphanumeric characters
Default:
Enter the text to display on the graphical front panel when the element being monitored is in an off/closed state. This
field is active when the
CONTENT
field is set to Status. The text displays when the status input is in the "off" state.
FONT
Range: 16, 18, 20
Default: 16
Set the font size to display on the graphical front panel.
TEXT COLOR
Range: 24-bit color selector
Default: Black
Set the text color to display in the specified cell.
BACK COLOR
Range: 24-bit color selector
Default: Grey
Set the background color to display for the specified cell.
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...