5.3.11.6 Event cause LED 1(9)
SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE LEDS
EVENT CAUSE LED 1(9)
For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.
LED 1 TYPE
— If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," the
LED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel
RESET
button, from a
remote device via a communications channel, or from any programmed operand.
The table outlines default input operand and output operands for each event cause LED.
Table 5-16: Default input and output operand for event cause LEDs
5.3.12 User-programmable self-tests
SETTINGS
PRODUCT SETUP
USER-PROGRAMMALBE SELF TESTS
EVENT CAUSE LED 1
LED 1 OPERAND:
LED PICKUP
Range: FlexLogic operand
LED 1 COLOR:
Green
Range: Red, Green, Orange
LED 1 TYPE:
Self-Reset
Range: Self-Reset, Latched
LED
Default input operand
Output operand
Default color
Event Cause LED 1
LED PICKUP
EVENT CAUSE LED 1
Green
Event Cause LED 2
LED VOLTAGE
EVENT CAUSE LED 2
Orange
Event Cause LED 3
LED CURRENT
EVENT CAUSE LED 3
Orange
Event Cause LED 4
LED FREQUENCY
EVENT CAUSE LED 4
Orange
Event Cause LED 5
LED OTHER
EVENT CAUSE LED 5
Orange
Event Cause LED 6
LED PHASE A
EVENT CAUSE LED 6
Orange
Event Cause LED 7
LED PHASE B
EVENT CAUSE LED 7
Orange
Event Cause LED 8
LED PHASE C
EVENT CAUSE LED 8
Orange
Event Cause LED 9
LED NEUTRAL/GROUND
EVENT CAUSE LED 9
Orange
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
RxGOOSE OFF
FUNCTION: Enabled
Range: Disabled, Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...