5-158
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM SETUP
CHAPTER 5: SETTINGS
5
3.
Configure source n (source 2 for this example) as the current from CTY in Winding 1 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(6)
settings menu.
SOURCE 2 NAME: “WDG 1Y”
SOURCE 2 PHASE CT: “F5”
SOURCE 2 GROUND CT: “None”
SOURCE 2 PHASE VT: “None”
SOURCE 2 AUX VT: “None”
4.
Configure source n (source 3 for this example) to be used as the current in Winding 2 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(6)
settings menu.
SOURCE 3 NAME: “WDG 2"
SOURCE 3 PHASE CT: “M1”
SOURCE 3 GROUND CT: “M1”
SOURCE 3 PHASE VT: “None”
SOURCE 3 AUX VT: “None”
5.
Configure the source setting of the transformer windings in the
SYSTEM SETUP
TRANSFORMER
WINDING n
settings menu.
WINDING 1 SOURCE: “WDG 1X”
WINDING 2 SOURCE: “WDG 1Y”
WINDING 3 SOURCE: “WDG 2"
Setup method B (alternate)
This approach adds the current from each phase of the CT1 and CT2 together to represent the total winding 1 current. The
procedure is outlined as follows.
1.
Enter the settings for each set of CTs in the
SYSTEM SETUP
AC INPUTS
CURRENT BANK
settings menu, as shown for
method A.
2.
Configure Source n (Source 1 for this example) to be used as the summed current in Winding 1 in the
SYSTEM SETUP
SIGNAL SOURCES
SOURCE n
settings menu.
SOURCE 1 NAME: “WDG 1"
SOURCE 1 PHASE CT: “F1 + F5”
SOURCE 1 GROUND CT: “None”
SOURCE 1 PHASE VT: “None”
SOURCE 1 AUX VT: “None”
3.
Configure Source n (Source 2 for this example) to be used as the Winding 2 current in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE n
settings menu.
SOURCE 2 NAME: “WDG 2"
SOURCE 2 PHASE CT: “M1”
SOURCE 2 GROUND CT: “M1”
SOURCE 2 PHASE VT: “None”
SOURCE 2 AUX VT: “None”
5.5.4.10 Transformer thermal inputs
SETTINGS
SYSTEM SETUP
TRANSFORMER
THERMAL INPUTS
THERMAL INPUTS
WINDING CURRENTS:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
(or the user-defined name)
AMBIENT TEMPERATURE:
RTD Input 1
Range: RTD Input 1, RTD Input 2,..., RTD Input 8, dcmA
Input 1, dcmA Input 2,..., dcmA Input 8, RRTD 1,
RRTD2,..., RRTD 12, Monthly Average
TOP-OIL TEMPERATURE:
RTD Input 1
Range: RTD Input 1, RTD Input 2,..., RTD Input 8, dcmA
Input 1, dcmA Input 2,..., dcmA Input 8, RRTD 1, RRTD2,...,
RRTD 12, Monthly Average
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...