CHAPTER 7: COMMANDS AND TARGETS
TARGETS MENU
T35 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
7-11
7
being the highest priority. For example, if all three SFP modules fail, then the third SFP target is activated. If the third
SFP module failure resolves, then the second SFP target is activated.
•
Latched target message
: No.
•
Description of problem
: The number of failures threshold was exceeded.
•
What to do
: Wait for the lockout interval and try to authenticate again.
•
Message
: "Unauthorized firmware attempt"
•
Latched target message
: No.
•
Description of problem
: A firmware upgrade operation was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the relay and try again.
•
Message
: "Unauthorized setting write"
•
Latched target message
: No.
•
Description of problem
: A setting write was attempted while the lock relay setting was enabled.
•
What to do
: Ask the Supervisor to unlock the settings and try again.
•
Message
: "An attempt to contact the Radius server has failed"
•
Latched target message
: No.
•
Description of problem
: The RADIUS authentication server is unavailable.
•
What to do
: Verify network connectivity and try again.
•
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
•
How often the test is performed: On relay power-up and afterwards once every 24 hours.
•
What to do: Contact the factory.
•
Description of problem
: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
•
What to do
: Update firmware to either of these builds.
•
7.2.2.4 HardFiber major self-test error messages
In addition to those provided by the standard UR-series devices, the UR devices implement HardFiber self-tests. These are
listed here. Any abnormal diagnostic condition indicated by the LEDs or the critical failure relay also results in a self-test
message, so troubleshooting is described here. For other relays, such at the B95
Plus
, see that product’s instruction manual.
AUTHENTICATION FAIL
FIRMWARE LOCK
SETTING LOCK
SERVER UNAVAILABLE
DOS PARTITION ALARM:
SELF-TEST ERROR
PROTOTYPE FIRMWARE:
Self Test Error
Содержание T35
Страница 9: ...TABLE OF CONTENTS T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ix ABBREVIATIONS INDEX ...
Страница 10: ...x T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 202: ...4 88 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 472: ...5 270 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 500: ...6 28 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 514: ...7 14 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 580: ...A 16 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 588: ...C 6 T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 596: ...iv T35 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...