NX-4V2 Control
23
74
EXPANDER TROUBLE / RESTORE COMM CODE
4............. numerical
Location 74 contains the digits for a 4+2 format that will be sent if "Expander Trouble Reporting" is enabled. Segments 1 & 2 contain
the digits of the "Expander Trouble Reporting". Segments 3 & 4 contain the digits of the "Expander Trouble Restore". (Box on pg 22.)
75
FAIL TO COMMUNICATE COMMUNICATOR CODE
2............. numerical
Location 75 contains the digits for a 4+2 format that will be sent if the "Fail To Communicate Reporting" is enabled. (Box on pg 22.)
76
LOG FULL COMMUNICATOR CODE
2............. numerical
Location 76 contains the digits for a 4+2 format if the "Log Full Reporting" is enabled. (Box on pg 22.)
77 OPENING
COMMUNICATOR CODE
8............. numerical
Location 77 contains the digit of a 4+2 format if the "Opening Reporting" is enabled.
(Box on pg 22.)
78 CLOSING
COMMUNICATOR CODE
8............. numerical
Location 78 contains the digit of a 4+2 format if the "Closing Reporting" is enabled. (Box on pg 22.)
79
AUTOTEST COMMUNICATOR CODE
2............. numerical
Location 79 contains the digits for a 4+2 format that will be sent if the "Autotest" or "Manual Test" is enabled. (Box on pg 22.)
80
RECENT CLOSING & EXIT ERROR COMM CODE
2............. numerical
Location 80 contains the digits for a 4+2 format that will be sent if "Recent Closing" and/or "Exit Error Reporting" is enabled. Segment
1 contains the digit for the "Recent Closing Reporting". Segment 2 contains the digit for the "Exit Error Reporting".
(Box on pg 22.)
81
START PROGRAM & END PROGRAM COMM CODES
4............. numerical
Location 81 contains the digits for a 4+2 format that will be sent if "Start / End Programming Reporting" is enabled. Segment 1
contains the digit for the "Start Program Reporting". Segment 2 contains the digit for the "Start Program Reporting". Segment 3
contains the digit for the "End Program Reporting". Segment 4 contains the digit for the "End Program Reporting". (Box on pg 22.)
82
END DOWNLOAD COMMUNICATOR CODE
4............. numerical
Location 82 contains the digits for a 4+2 format that will be sent if "End Downloading Reporting" is enabled. Segments 1 and 2 are
Reserved
. Segment 3 contains the digit of the "End Download Reporting". Segment 4 contains the digit of the "End Download
Reporting". (Box on pg 22.)
Note
: A start download report will be sent to the internal event log.
83
CANCEL COMMUNICATOR CODE
1............. numerical
Location 83 contains the digit for a 4+2 format that will be sent if "Cancel Reporting" is enabled. Segment 1 contains the digit for the
"Cancel Communicator Reporting".
(Box on pg 22.)
84-109
RESERVED
LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE TYPES (Configurations) AS LISTED IN THE TABLE
ON PAGE 16. THESE LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD
ONLY BE CHANGED WITH A THOROUGH UNDERSTANDING OF THE OPERATION OF EACH BIT.
110
ZONE TYPE 1 ALARM EVENT CODE
1............. numerical
Location 110 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 16. The zone ID will be that zone that is in alarm.
4+2 Format Note
: If 4+2 format is being used, the number programmed in this location will be sent as the upper hex digit. The digit in
location 110 should be from 1 to 15 when using 4+2 formats. The zone ID or user ID will be the lower hex digit of the zone that is in
alarm.
111
ZONE TYPE 1 CHARACTERISTIC SELECT
5............. feature select
Segment 1:
1 = Fire (turn on if this is a fire zone).
2 = 24 hour (turn on for non-fire 24 hour zones).
3 = Keyswitch zone. (normally open switch)
4 = Follower (turn on for burglary zones that are Instant during non-entry times).
5 = Delay 1 zone (follows timer 1 entry and exit times).
6 = Delay 2 zone (follows timer 2 entry and exit times).
7 = Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming).
8 = Local only (turn on if this zone should not be reported).
Segment 2:
1 = On if Zone Type will beep the keypad for alarm.
2 = On if Zone Type will sound the yelping siren for alarm.
3 = On if Zone Type will sound the temporal siren for alarm.
4 = On if Zone Type will chime.
WWW.DIYALARMFORUM.COM