5-104
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
The UR implementation of IEC 60870-5-103 consists of the following functions:
•
Report binary inputs
•
Report analog values (measurands)
•
Commands
•
Time synchronization
The RS485 port supports IEC 60870-5-103.
The UR Family Communications Guide contains more information on the protocol.
IEC103 COMMON ADDRESS OF ASDU
— This setting uniquely defines this M60 on the serial line. Select an ID between 0 and
254. This ID does not need to be in sequential order for all stations that communicate with a controller, but it is
recommended. Note that RS485 only allows a maximum of 32 slave stations on a communication line, so the entire range
of 254 addresses is never exhausted.
IEC103 SYNC TIMEOUT
— This setting defines the time that the M60 waits for a synchronization message. The M60
synchronizes its clock using all available sources, with the source synching more frequently overwriting the time of the
other sources. Since the synchronization message received from the IEC 60870-5-103 master is less frequent than IRIG-B,
PTP, or SNTP, its time is overwritten by these three sources, if any of them is active. If the synchronization timeout occurs
and none of IRIG-B, PTP, or SNTP is active, the M60 sets the invalid bit in the time stamp of a time-tagged message.
The settings for the remaining menus are outlined as follows.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 60870-5-103
IEC103 INPUTS BINARY
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
IEC103 INPUTS
BINARY
POINT 0
See below
POINT 1
See below
POINT 95
See below
POINT 0
POINT 0 FUN
0
Range: 0 to 255 in steps of 1
POINT 0 INF
0
Range: 0 to 255 in steps of 1
POINT 0 Input
Off
Range: FlexLogic operand
POINT 95
POINT 95 FUN
0
Range: 0 to 255 in steps of 1
POINT 95 INF
0
Range: 0 to 255 in steps of 1
POINT 95 Input
Off
Range: FlexLogic operand
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...