5-50
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
The tables outline the information displayed when the two submenus are selected.
Table 5-7: Routing table information
Table 5-8: IP ARP information
5.3.5.8 Modbus protocol
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
MODBUS PROTOCOL
The serial communication ports utilize the Modbus protocol, unless the port is configured for DNP or IEC 60870-5-103
operation. This allows the EnerVista UR Setup software to be used on the port. UR devices operate as Modbus slave
devices only.
For more information on the protocol, including the memory map table, see the UR Family Communications Guide.
MODBUS SLAVE ADDRESS
— When using the Modbus protocol on the RS232 port, the M60 responds regardless of the
MODBUS SLAVE ADDRESS
programmed. For the RS485 port, each device on the serial bus must have a unique slave address
from 1 to 254. Address 0 and addresses from 248 and up are reserved by the Modbus protocol specification, and so their
use here is not recommended. Address 0 is the broadcast address to which all Modbus slave devices listen. Addresses do
not have to be sequential, but no two devices can have the same address or conflicts resulting in errors occur. Generally,
starting at 1, set each device added to the link to use the next higher address. When using Modbus TCP/IP, the client must
use the programmed
MODBUS SLAVE ADDRESS
value in the Unit Identifier field.
MODBUS TCP PORT NUMBER
— Modbus over TCP/IP can also be used on any of the Ethernet ports. The listening TCP port 502
is reserved for Modbus communications, and only in exceptional cases when
MODBUS TCP PORT NUMBER
is set to any other
port. The
MODBUS TCP PORT NUMBER
setting sets the TCP port used by Modbus on Ethernet. A
MODBUS TCP PORT NUMBER
of
0 disables Modbus over TCP/IP, meaning closes the Modbus TCP port. When the port number is changed to 0, the change
takes effect when the M60 is restarted. When it is set to 0, use the front panel or serial port to communicate with the relay.
5.3.5.9 Protocol selection
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
PROTOCOL
Field
Description
Destination
The IP address of the remote network to which this route points
Mask
The network mask for the destination
Gateway
The IP address of the next router to the remote network
Interface
Interface through which the specified network can be reached
Field
Description
IP Address
The network address that corresponds to Hardware Address
Age (min)
Age, in minutes, of the cache entry. A hyphen (-) means the address is local.
Hardware Address
LAN hardware address, a MAC address that corresponds to network address
Type
Dynamic or Static
Interface
Interface to which this address mapping has been assigned
MODBUS PROTOCOL
MODBUS SLAVE
ADDRESS: 254
Range: 1 to 254 in steps of 1
MODBUS TCP PORT
NUMBER(502): 502
Range: 0 to 65535 in steps of 1
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
PROTOCOL
SCADA PROTOCOL:
DNP 3.0
Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...