5-26
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
LANGUAGE
— This setting selects the language used to display settings, actual values, and targets. This setting displays
when a language other than English was purchased, and the range depends on the order code of the relay.
With the graphical front panel, the language can be changed regardless of the language purchased. That is, all languages
can be used. If you select a language with which you are unfamiliar and want to switch back to English for example, the
menu order remains the same. That is, Settings is always second, Product Setup is always first, Display Properties is always
second, and Language is always first.
The language can be selected also for the front panel in EnerVista under
Maintenance > Change Front Panel
.
The language of the EnerVista software can be changed under
View > Language
.
FLASH MESSAGE TIME
— Flash messages are status, warning, error, and information messages displayed in response to
certain key presses during settings programming. These messages override any normal messages. Use this setting to
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT
— If the keypad is inactive for a period of time, the relay automatically reverts to a default
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough
during programming or reading of actual values. This setting is not supported on the graphical front panel.
DEFAULT MESSAGE INTENSITY
— To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
This setting is not supported on the graphical front panel.
SCREEN SAVER FEATURE
and
SCREEN SAVER WAIT TIME
— These settings are only visible if the M60 has a liquid crystal display
(LCD) and control its backlighting. When the
SCREEN SAVER FEATURE
is “Enabled,” the LCD backlighting turns off after the
DEFAULT MESSAGE TIMEOUT
followed by the
SCREEN SAVER WAIT TIME
, provided that no keys have been pressed and no
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on. These
settings are not supported on the graphical front panel.
CURRENT CUT-OFF LEVEL
— This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value)
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to
display even when the value reflects noise rather than the actual signal. The M60 applies a cut-off value to the magnitudes
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the
cut-off level for the sensitive ground input is 10 times lower that the
CURRENT CUT-OFF LEVEL
setting value. Raw current
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL
— This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero,
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The M60
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level,
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off
operation applies to quantities used for metering, protection, and control, as well as those used by communications
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
The
CURRENT CUT-OFF LEVEL
and the
VOLTAGE CUT-OFF LEVEL
are used to determine the metered power cut-off levels. The
power cut-off level is calculated using the following equations. For Delta connections:
Eq. 5-3
For Wye connections:
Eq. 5-4
Eq. 5-5
where VT primary = VT secondary
×
VT ratio and CT primary = CT secondary
×
CT ratio.
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...