5-176
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
LED INDICATORS:
Enhanced and
standard front panels
LED IN SERVICE
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
Asserted when the front panel IN SERVICE LED is on
Asserted when the front panel TROUBLE LED is on
Asserted when the front panel TEST MODE LED is on
Asserted when the front panel TRIP LED is on
Asserted when the front panel ALARM LED is on
Asserted when an element picks up and to turn PICKUP LED on
Asserted when a voltage element involved and to turn VOLTAGE LED on
Asserted when a current element involved and to turn CURRENT LED on
Asserted when a frequency element involved and to turn FREQUENCY LED on
Asserted when a composite element involved and to turn OTHER LED on
Asserted when phase A involved and to turn PHASE A LED on
Asserted when phase B involved and to turn PHASE B LED on
Asserted when phase C involved and to turn PHASE C LED on
Asserted when a neutral or ground element involved and to turn NEUTRAL/
GROUND LED on
LED INDICATORS:
Graphical front panel
LED IN SERVICE
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
Asserted when the front panel IN SERVICE LED is on
Asserted when the front panel TROUBLE LED is on
Asserted when the front panel TEST MODE LED is on
Asserted when the front panel TRIP LED is on
Asserted when the front panel ALARM LED is on
Asserted when an element picks up and to turn Event Cause LED 1 on by
default
Asserted when a voltage element involved and to turn Event Cause LED 2 on
by default
Asserted when a current element involved and to turn Event Cause LED 3 on
by default
Asserted when a frequency element involved and to turn Event Cause LED 4
on by default
Asserted when a composite element involved and to turn Event Cause LED 5
on by default
Asserted when phase A involved and to turn Event Cause LED 6 on by default
Asserted when phase B involved and to turn Event Cause LED 7 on by default
Asserted when phase C involved and to turn Event Cause LED 8 on by default
Asserted when a neutral or ground element involved and to turn Event Cause
LED 9 on by default
LED INDICATORS:
LED test
LED TEST IN PROGRESS
An LED test has been initiated and has not finished
LED INDICATORS:
User-programmable
LEDs
Enhanced and
standard front panels
LED USER 1
Asserted when user-programmable LED 1 is on
LED USER 2 to 48
The operand above is available for user-programmable LEDs 2 through 48
LED INDICATORS:
User-programmable
LEDs
Graphical front panel
EVENT CAUSE LED 1
Asserted when event cause LED 1 is on
EVENT CAUSE LED 2 to 9
Same operand as EVENT CAUSE LED 1
PASSWORD
SECURITY
ACCESS LOC SETG OFF
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
Asserted when local setting access is disabled
Asserted when local setting access is enabled
Asserted when local command access is disabled
Asserted when local command access is enabled
Asserted when remote setting access is disabled
Asserted when remote setting access is enabled
Asserted when remote command access is disabled
Asserted when remote command access is enabled
Asserted when a password entry fails while accessing a password protected
level of the M60
RxGOOSE
RxGOOSE 1 On
↓
RxGOOSE 64 On
Flag is set, logic=1
↓
Flag is set, logic=1
RxGOOSE 1 Off
↓
RxGOOSE 64 Off
Flag is set, logic=1
↓
Flag is set, logic=1
Operand type
Operand syntax
Operand description
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...