5-172
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
ELEMENT:
Phase time
overcurrent
PHASE TOC1 PKP
PHASE TOC1 OP
PHASE TOC1 DPO
PHASE TOC1 PKP A
PHASE TOC1 PKP B
PHASE TOC1 PKP C
PHASE TOC1 OP A
PHASE TOC1 OP B
PHASE TOC1 OP C
PHASE TOC1 DPO A
PHASE TOC1 DPO B
PHASE TOC1 DPO C
At least one phase of phase time overcurrent 1 has picked up
At least one phase of phase time overcurrent 1 has operated
All phases of phase time overcurrent 1 have dropped out
Phase A of phase time overcurrent 1 has picked up
Phase B of phase time overcurrent 1 has picked up
Phase C of phase time overcurrent 1 has picked up
Phase A of phase time overcurrent 1 has operated
Phase B of phase time overcurrent 1 has operated
Phase C of phase time overcurrent 1 has operated
Phase A of phase time overcurrent 1 has dropped out
Phase B of phase time overcurrent 1 has dropped out
Phase C of phase time overcurrent 1 has dropped out
PHASE TOC2 to 6
Same set of operands as shown for PHASE TOC1
ELEMENT:
Phase undervoltage
PHASE UV1 PKP
PHASE UV1 OP
PHASE UV1 DPO
PHASE UV1 PKP A
PHASE UV1 PKP B
PHASE UV1 PKP C
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
PHASE UV1 DPO A
PHASE UV1 DPO B
PHASE UV1 DPO C
At least one phase of phase undervoltage 1 has picked up
At least one phase of phase undervoltage 1 has operated
All phases of phase undervoltage 1 have dropped out
Phase A of phase undervoltage 1 has picked up
Phase B of phase undervoltage 1 has picked up
Phase C of phase undervoltage 1 has picked up
Phase A of phase undervoltage 1 has operated
Phase B of phase undervoltage 1 has operated
Phase C of phase undervoltage 1 has operated
Phase A of phase undervoltage 1 has dropped out
Phase B of phase undervoltage 1 has dropped out
Phase C of phase undervoltage 1 has dropped out
PHASE UV2 to 3
Same set of operands as shown for PHASE UV1
ELEMENT:
Reduced voltage
starting
REDUCED VOLT CTRL
REDUCED VOLT OP
Asserted for one second upon a valid transition in any mode
Asserted when an invalid transition occurs
ELEMENT:
Restart delay
RESTART TIME OP
The minimum restart time has not expired since the last motor stop. No
restart is allowed when this operand is asserted (use to inhibit the motor start
command).
ELEMENT:
Broken rotor bar
detection
ROTOR ALARM PKP
ROTOR ALARM OP
Asserted when the broken rotor bar detection element picks up
Asserted when the broken rotor bar detection element operates
ELEMENT:
Remote RTD
protection
RRTD COMM FAIL
RRTD RTD 1 ALARM DPO
RRTD RTD 1 ALARM OP
RRTD RTD 1 ALARM PKP
RRTD RTD 1 OPEN
RRTD RTD 1 SHORTED
RRTD RTD 1 TRIP DPO
RRTD RTD 1 TRIP OP
RRTD RTD 1 TRIP PKP
Asserted when RRTD loss of communications is detected
Asserted when the RRTD RTD 1 alarm stage drops out
Asserted when the RRTD RTD 1 alarm stage operates
Asserted when the RRTD RTD 1 alarm stage picks up
Asserted when the RRTD RTD 1 detects an open circuit
Asserted when the RRTD RTD 1 detects an short/low circuit
Asserted when the RRTD RTD 1 trip stage drops out
Asserted when the RRTD RTD 1 trip stage operates
Asserted when the RRTD RTD 1 trip stage picks up
RRTD RTD 2 to 12
The set of operands shown are available for RRTD RTD 2 and higher
ELEMENT:
RTD protection
RTD Ip 1 ALARM DPO
RTD Ip 1 ALARM OP
RTD Ip 1 ALARM PKP
RTD Ip 1 OPEN
RTD Ip 1 SHORTED
RTD Ip 1 TRIP DPO
RTD Ip 1 TRIP OP
RTD Ip 1 TRIP PKP
Asserted when the alarm stage of RTD input 1 protection picks up
Asserted when the alarm stage of RTD input 1 protection operates
Asserted when the alarm stage of RTD input 1 protection drops out
Asserted when RTD input 1 detects an open circuit
Asserted when RTD input 1 detects a shorted or low circuit
Asserted when the trip stage of RTD input 1 protection picks up
Asserted when the trip stage of RTD input 1 protection operates
Asserted when the trip stage of RTD input 1 protection drops out
RTD Ip 2 to 48
The set of operands shown are available for the RTD Ip 2 and higher elements
Operand type
Operand syntax
Operand description
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...