CHAPTER 5: SETTINGS
FLEXLOGIC
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5-173
5
ELEMENT:
Selector switch
SELECTOR 1 POS Y
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
SELECTOR 2
Same set of operands as shown for SELECTOR 1
ELEMENT:
Setting group
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
ELEMENT:
Disturbance detector
SRC1 50DD OP
SRC2 50DD OP
SRC3 50DD OP
SRC4 50DD OP
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
ELEMENT:
VTFF (Voltage
transformer fuse
failure)
SRC1 VT FF OP
SRC1 VT FF DPO
SRC1 VT FF VOL LOSS
SRC1 VT FF ALARM
Source 1 VT fuse failure detector has operated
Source 1 VT fuse failure detector has dropped out
Source 1 has lost voltage signals (V2 below 10% and V1 below 5% of nominal)
Source 1 has triggered a VT fuse failure alarm
SRC1 VT NEU WIRE OPEN
Source 1 VT neutral wire open detected. When the VT is connected in Delta,
do not enable this function because there is no neutral wire for Delta
connected VT.
SRC2 VT FUSE FAIL to SRC4
Same set of operands as shown for SRC1 VT FF
ELEMENT:
Starts-per-hour
STARTS-PER-HOUR PKP
STARTS-PER-HOUR OP
STARTS-PER-HOUR DPO
The maximum starting rate has been exceeded. No immediate start is
allowed if the motor stops when this operand is asserted.
The motor stopped after the last allowable start. No restart is allowed as long
as the operand is asserted (used to inhibit the motor start command).
The maximum starting rate is not exceeded. When stopped, the motor can be
restarted immediately.
ELEMENT:
Stator differential
STATOR DIFF OP
STATOR DIFF PKP A
STATOR DIFF PKP B
STATOR DIFF PKP C
STATOR DIFF OP A
STATOR DIFF OP B
STATOR DIFF OP C
STATOR DIFF DPO A
STATOR DIFF DPO B
STATOR DIFF DPO C
STATOR DIFF SAT A
STATOR DIFF SAT B
STATOR DIFF SAT C
STATOR DIFF DIR A
STATOR DIFF DIR B
STATOR DIFF DIR C
At least one phase of stator differential has operated
Phase A of stator differential has picked up
Phase B of stator differential has picked up
Phase C of stator differential has picked up
Phase A of stator differential has operated
Phase B of stator differential has operated
Phase C of stator differential has operated
Phase A of stator differential has dropped out
Phase B of stator differential has dropped out
Phase C of stator differential has dropped out
Phase A of stator differential has is saturated
Phase B of stator differential has is saturated
Phase C of stator differential has is saturated
Phase A of stator differential phase comparison has been satisfied
Phase B of stator differential phase comparison has been satisfied
Phase C of stator differential phase comparison has been satisfied
Operand type
Operand syntax
Operand description
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...