5-170
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 5: SETTINGS
5
CT FAIL 2 to 4
Same set of operands as per CT FAIL 1
ELEMENT:
Digital counters
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Digital counter 1 output is ‘more than’ comparison value
Digital counter 1 output is ‘equal to’ comparison value
Digital counter 1 output is ‘less than’ comparison value
Counter 2 to 8
Same set of operands as shown for Counter 1
ELEMENT:
Digital elements
Dig Element 1 PKP
Dig Element 1 OP
Dig Element 1 DPO
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Dig Element 2 to 48
Same set of operands as shown for Dig Element 1
ELEMENT:
Sensitive directional
power
DIR POWER 1 STG1 PKP
DIR POWER 1 STG2 PKP
DIR POWER 1 STG1 DPO
DIR POWER 1 STG2 DPO
DIR POWER 1 STG1 OP
DIR POWER 1 STG2 OP
DIR POWER 1 PKP
DIR POWER 1 DPO
DIR POWER 1 OP
Stage 1 of the directional power element 1 has picked up
Stage 2 of the directional power element 1 has picked up
Stage 1 of the directional power element 1 has dropped out
Stage 2 of the directional power element 1 has dropped out
Stage 1 of the directional power element 1 has operated
Stage 2 of the directional power element 1 has operated
The directional power element has picked up
The directional power element has dropped out
The directional power element has operated
DIR POWER 2
Same set of operands as DIR POWER 1
ELEMENT:
FlexElements
FxE 1 PKP
FxE 1 OP
FxE 1 DPO
FlexElement 1 has picked up
FlexElement 1 has operated
FlexElement 1 has dropped out
FxE 2 to 16
Same set of operands as shown for FxE 1
ELEMENT:
Ground
instantaneous
overcurrent
GROUND IOC1 PKP
GROUND IOC1 OP
GROUND IOC1 DPO
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
GROUND IOC2 to 12
Same set of operands as shown for GROUND IOC 1
ELEMENT:
Ground time
overcurrent
GROUND TOC1 PKP
GROUND TOC1 OP
GROUND TOC1 DPO
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
GROUND TOC2 to 6
Same set of operands as shown for GROUND TOC1
ELEMENT:
Non-volatile latches
LATCH 1 ON
LATCH 1 OFF
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to 16
Same set of operands as shown for LATCH 1
ELEMENT:
Motor mechanical
jam
MECHANICAL JAM PKP
MECHANICAL JAM DPO
MECHANICAL JAM OP
The mechanical jam element has picked up
The mechanical jam element has dropped out
The mechanical jam element has operated
ELEMENT:
Motor acceleration
time
MOTOR ACCEL TIME OP
MOTOR ACCEL TIME DPO
The motor acceleration time element has operated
The motor acceleration time element has dropped out
ELEMENT:
Two-speed motor
MOTOR SPD2 TR 2-1 OP
MOTOR SPD2 ACL t OP
MOTOR SPD2 ACL t DPO
Asserted when the motor switches from speed 2 to speed 1
Asserted when the acceleration time function at speed 2 operates
Asserted when the acceleration time function at speed 2 drops off
ELEMENT:
Motor thermal model
MOTOR THERMAL PKP
MOTOR THERMAL OP
MOTOR THERMAL DPO
MOTOR RESTART
MOTOR START INHIBIT
MOTOR OFFLINE
MOTOR STARTING
MOTOR RUNNING
MOTOR OVERLOAD
The thermal model element has picked up
The thermal model element has operated
The thermal model element has dropped out
The motor has restarted
A motor start inhibit condition has occurred
The motor is offline
The motor is starting
The motor is running
A motor overload condition has occurred
ELEMENT:
Negative-sequence
overvoltage
NEG SEQ OV1 PKP
NEG SEQ OV1 DPO
NEG SEQ OV1 OP
Negative-sequence overvoltage element has picked up
Negative-sequence overvoltage element has dropped out
Negative-sequence overvoltage element has operated
NEG SEQ OV2 to 3
Same set of operands as shown for NEG SEQ OV1
Operand type
Operand syntax
Operand description
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...