GE Multilin
M60 Motor Protection System
2-27
2 PRODUCT DESCRIPTION
2.3 SPECIFICATIONS
2
2.3.11 TYPE TESTS
M60 TYPE TESTS
2.3.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
TEST
REFERENCE STANDARD
TEST LEVEL
Dielectric voltage withstand
EN60255-5
2.2 kV
Impulse voltage withstand
EN60255-5
5 kV
Damped oscillatory
IEC61000-4-18 / IEC60255-22-1
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN61000-4-2 / IEC60255-22-2
Level 3
RF immunity
EN61000-4-3 / IEC60255-22-3
Level 3
Fast transient disturbance
EN61000-4-4 / IEC60255-22-4
Class A and B
Surge immunity
EN61000-4-5 / IEC60255-22-5
Level 3 and 4
Conducted RF immunity
EN61000-4-6 / IEC60255-22-6
Level 3
Power frequency immunity
EN61000-4-7 / IEC60255-22-7
Class A and B
Voltage interruption and ripple DC
IEC60255-11
12% ripple, 200 ms interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC60255-25
Class A
Sinusoidal vibration
IEC60255-21-1
Class 1
Shock and bump
IEC60255-21-2
Class 1
Seismic
IEC60255-21-3
Class 1
Power magnetic immunity
IEC61000-4-8
Level 5
Pulse magnetic immunity
IEC61000-4-9
Level 4
Damped magnetic immunity
IEC61000-4-10
Level 4
Voltage dip and interruption
IEC61000-4-11
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory
IEC61000-4-12
2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz
IEC61000-4-16
Level 4
Voltage ripple
IEC61000-4-17
15% ripple
Ingress protection
IEC60529
IP40 front, IP10 back
Cold
IEC60068-2-1
–40°C for 16 hours
Hot
IEC60068-2-2
85°C for 16 hours
Humidity
IEC60068-2-30
6 days, variant 1
Damped oscillatory
IEEE/ANSI C37.90.1
2.5 kV, 1 MHz
RF immunity
IEEE/ANSI C37.90.2
20 V/m, 80 MHz to 1 GHz
Safety
UL508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
Safety
UL1053
e83849 NKCR
Содержание M60 UR Series
Страница 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Страница 98: ...3 40 M60 Motor Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 238: ...5 110 M60 Motor Protection System GE Multilin 5 4 SYSTEM SETUP 5 SETTINGS 5 Figure 5 29 DISCONNECT SWITCH SCHEME LOGIC ...
Страница 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 413: ...GE Multilin M60 Motor Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 29 ...
Страница 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Страница 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Страница 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...