GE Multilin
M60 Motor Protection System
B-27
APPENDIX B
B.4 MEMORY MAPPING
B
408B
Port 1 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
408D
Network Address NSAP
---
---
---
F074
0
4097
Port 1 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4098
Port 2 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4099
Port 3 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
409A
DNP Channel 1 Port
0 to 5
---
1
F177
0 (None)
409B
DNP Channel 2 Port
0 to 5
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
0 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
0 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
0 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
0 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP Unsolicited Responses Maximum Retries
1 to 255
---
1
F001
10
40AC
DNP Unsolicited Responses Destination Address
0 to 65519
---
1
F001
1
40AD
Ethernet Operation Mode
0 to 1
---
1
F192
1 (Half-Duplex)
40AE
DNP Current Scale Factor
0 to 8
---
1
F194
2 (1)
40AF
DNP Voltage Scale Factor
0 to 8
---
1
F194
2 (1)
40B0
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B1
DNP Energy Scale Factor
0 to 8
---
1
F194
2 (1)
40B2
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B3
DNP Other Scale Factor
0 to 8
---
1
F194
2 (1)
40B4
DNP Current Default Deadband
0 to 100000000
---
1
F003
30000
40B6
DNP Voltage Default Deadband
0 to 100000000
---
1
F003
30000
40B8
DNP Power Default Deadband
0 to 100000000
---
1
F003
30000
40BA
DNP Energy Default Deadband
0 to 100000000
---
1
F003
30000
40BC
DNP Power Factor Default Deadband
0 to 100000000
--
1
F003
30000
40BE
DNP Other Default Deadband
0 to 100000000
---
1
F003
30000
40C0
DNP IIN Time Synchronization Bit Period
1 to 10080
min
1
F001
1440
40C1
DNP Message Fragment Size
30 to 2048
---
1
F001
240
40C2
DNP Client Address 3
0 to 4294967295
---
1
F003
0
40C4
DNP Client Address 4
0 to 4294967295
---
1
F003
0
40C6
DNP Client Address 5
0 to 4294967295
---
1
F003
0
40C8
DNP Number of Paired Binary Output Control Points
0 to 32
---
1
F001
0
40C9
DNP TCP Connection Timeout
10 to 65535
---
1
F001
120
40CA
DNP Communications Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
0 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 Protocol Function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 Protocol Cyclic data Transmit Period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 Current Default Threshold
0 to 100000000
---
1
F003
30000
40E6
IEC 60870-5-104 Voltage Default Threshold
0 to 100000000
---
1
F003
30000
40E8
IEC 60870-5-104 Power Default Threshold
0 to 100000000
---
1
F003
30000
40EA
IEC 60870-5-104 Energy Default Threshold
0 to 100000000
---
1
F003
30000
40EC
IEC 60870-5-104 Power Default Threshold
0 to1
---
0.01
F001
100
40EE
IEC 60870-5-104 Other Default Threshold
0 to 100000000
---
1
F003
30000
40F0
IEC 60870-5-104 Client Address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 Redundancy Port
0 to 1
---
1
F126
0 (No)
4105
Port 2 IP Address
0 to 4294967295
---
1
F003
56554706
4107
Port 2 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание M60 UR Series
Страница 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Страница 98: ...3 40 M60 Motor Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 238: ...5 110 M60 Motor Protection System GE Multilin 5 4 SYSTEM SETUP 5 SETTINGS 5 Figure 5 29 DISCONNECT SWITCH SCHEME LOGIC ...
Страница 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 413: ...GE Multilin M60 Motor Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 29 ...
Страница 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Страница 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Страница 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 662: ...x M60 Motor Protection System GE Multilin INDEX ...