B-54
M60 Motor Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
AA77
...Repeated for IEC 61850 GOOSE analog input 18
AA7E
...Repeated for IEC 61850 GOOSE analog input 19
AA85
...Repeated for IEC 61850 GOOSE analog input 20
AA8C
...Repeated for IEC 61850 GOOSE analog input 21
AA93
...Repeated for IEC 61850 GOOSE analog input 22
AA9A
...Repeated for IEC 61850 GOOSE analog input 23
AAA1
...Repeated for IEC 61850 GOOSE analog input 24
AAA8
...Repeated for IEC 61850 GOOSE analog input 25
AAAF
...Repeated for IEC 61850 GOOSE analog input 26
AAB6
...Repeated for IEC 61850 GOOSE analog input 27
AABD
...Repeated for IEC 61850 GOOSE analog input 28
AAC4
...Repeated for IEC 61850 GOOSE analog input 29
AACB
...Repeated for IEC 61850 GOOSE analog input 30
AAD2
...Repeated for IEC 61850 GOOSE analog input 31
AAD9
...Repeated for IEC 61850 GOOSE analog input 32
IEC 61850 XCBR configuration (read/write settings) (6 Modules)
AB00
Operand for IEC 61850 XCBR1.ST.Loc status
0 to 4294967295
---
1
F300
0
AB02
Command to clear XCBR1 OpCnt (operation counter)
0 to 1
---
1
F126
0 (No)
AB03
Operand for IEC 61850 XCBR Check Sync Release
0 to 4294967295
---
1
F300
0
AB05
Operand for IEC 6185 XCBR Open Interlock
0 to 4294967295
---
1
F300
0
AB07
Operand for IEC 61850 XCBR Close Interlock
0 to 4294967295
---
1
F300
0
AB09
Operand for IEC 61850 XCBR Pos ct1Model
0 to 4
---
1
F001
2
AB0A
Operand for IEC 61850 XCBR Pos sboTimeout
2 to 60
s
1
F001
30
AB0B
...Repeated for Module 2
AB16
...Repeated for Module 3
AB21
...Repeated for Module 4
AB2C
...Repeated for Module 5
AB37
...Repeated for Module 6
IEC 61850 LN name prefixes (Read/Write Settings)
AB48
IEC 61850 logical node LPHD1 name prefix
0 to 65534
---
1
F206
(none)
AB4B
IEC 61850 logical node PIOCx name prefix (72 items)
0 to 65534
---
1
F206
(none)
AC23
IEC 61850 logical node PTOCx name prefix (24 items)
0 to 65534
---
1
F206
(none)
AC6B
IEC 61850 logical node PTUVx name prefix (13 items)
0 to 65534
---
1
F206
(none)
AC92
IEC 61850 logical node PTOVx name prefix (10 items)
0 to 65534
---
1
F206
(none)
ACB0
IEC 61850 logical node PDISx name prefix (10 items)
0 to 65534
---
1
F206
(none)
ACCE
IEC 61850 logical node RBRFx name prefix (24 items)
0 to 65534
---
1
F206
(none)
AD16
IEC 61850 logical node RPSBx name prefix
0 to 65534
---
1
F206
(none)
AD19
IEC 61850 logical node RRECx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD2B
IEC 61850 logical node MMXUx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD3D
IEC 61850 logical node GGIOx name prefix (5 items)
0 to 65534
---
1
F206
(none)
AD4C
IEC 61850 logical node RFLOx name prefix (5 items)
0 to 65534
---
1
F206
(none)
AD5B
IEC 61850 logical node XCBRx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD6D
IEC 61850 logical node PTRCx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD7F
IEC 61850 logical node PDIFx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AD8B
IEC 61850 logical node MMXNx name prefix (6 items)
0 to 65534
---
1
F206
(none)
ADFA
IEC 61850 logical node CSWIx name prefix (6 items)
0 to 65534
---
1
F206
(none)
AE54
IEC 61850 logical node XSWIx name prefix (6 items)
0 to 65534
---
1
F206
(none)
IEC 61850 GGIO4 General Analog Configuration Settings (Read/Write)
AF00
Number of analog points in GGIO4
4 to 32
---
4
F001
4
AF01
GOOSE analog scan period
100 to 5000
---
10
F001
1000
IEC 61850 GGIO4 Analog Input Points Configuration Settings (Read/Write)
AF10
IEC 61850 GGIO4 analog input 1 value
---
---
---
F600
0
AF11
IEC 61850 GGIO4 analog input 1 deadband
0.001 to 100
%
0.001
F003
100000
Table B–9: MODBUS MEMORY MAP (Sheet 47 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание M60 UR Series
Страница 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Страница 98: ...3 40 M60 Motor Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 238: ...5 110 M60 Motor Protection System GE Multilin 5 4 SYSTEM SETUP 5 SETTINGS 5 Figure 5 29 DISCONNECT SWITCH SCHEME LOGIC ...
Страница 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 413: ...GE Multilin M60 Motor Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 29 ...
Страница 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Страница 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Страница 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...