B-28
M60 Motor Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
4109
Port 2 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
410B
PRT2 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
410C
PRT2 Redundancy Enabled
0 to 2
---
1
F627
0 (None)
410D
Port 3 IP Address
0 to 4294967295
---
1
F003
56554706
410F
Port 3 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4111
Port 3 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
4113
Port 3 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
4114
PRT1 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4115
PRT2 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4116
PRT3 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4119
PRT2 PRP Mcst Addr
---
---
---
F072
0
411C
IEC Communications Reserved (33 items)
0 to 1
---
1
F001
0
413E
High Enet Traffic Function
0 to 1
---
1
F102
0 (Disabled)
413F
High Enet Traffic Events
0 to 1
---
1
F102
0 (Disabled)
4140
DNP Object 1 Default Variation
1 to 2
---
1
F001
2
4141
DNP Object 2 Default Variation
1 to 3
---
1
F001
2
4142
DNP Object 20 Default Variation
0 to 3
---
1
F523
0 (1)
4143
DNP Object 21 Default Variation
0 to 3
---
1
F524
0 (1)
4144
DNP Object 22 Default Variation
0 to 3
---
1
F523
0 (1)
4145
DNP Object 23 Default Variation
0 to 3
---
1
F523
0 (1)
4146
DNP Object 30 Default Variation
1 to 5
---
1
F001
1
4147
DNP Object 32 Default Variation
0 to 5
---
1
F525
0 (1)
4148
SCADA Protocol
0 to 2
---
1
F629
0 (DNP 3.0)
Communications Actuals (Read Only)
4160
Modbus Available TCP/IP Connections
0 to 4
---
1
F001
4
4161
DNP Available TCP/IP Connections
0 to 2
---
1
F001
2
4162
IEC Available TCP/IP Connections
0 to 2
---
1
F001
2
4163
MMS Available TCP/IP Connections
0 to 5
---
1
F001
5
4164
PMU Available TCP/IP Connections
0 to 4
---
1
F001
4
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
0 to 1
---
1
F102
0 (Disabled)
4169
Simple Network Time Protocol (SNTP) Server IP Address
0 to 4294967295
---
1
F003
0
416B
Simple Network Time Protocol (SNTP) UDP Port Number
1 to 65535
---
1
F001
123
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
0 to 1
---
1
F126
0 (No)
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
---
---
---
F600
0
4191
Data Logger Mode
0 to 1
---
1
F260
0 (continuous)
4192
Data Logger Trigger
0 to 4294967295
---
1
F300
0
4194
Data Logger Rate
15 to 3600000
ms
1
F003
60000
Clock (Read/Write Setting)
419F
Synchronizing Source
0 to 3
---
1
F623
0 (none)
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
0 to 235959
---
1
F050
0
Clock (Read/Write Setting)
41A2
SR Date Format
0 to 4294967295
---
1
F051
0
41A4
SR Time Format
0 to 4294967295
---
1
F052
0
41A6
IRIG-B Signal Type
0 to 2
---
1
F114
0 (None)
41A7
Clock Events Enable / Disable
0 to 1
---
1
F102
0 (Disabled)
41A8
Time Zone Offset from UTC
–24 to 24
hours
0.5
F002
0
41A9
Daylight Savings Time (DST) Function
0 to 1
---
1
F102
0 (Disabled)
41AA
Daylight Savings Time (DST) Start Month
0 to 11
---
1
F237
0 (January)
41AB
Daylight Savings Time (DST) Start Day
0 to 6
---
1
F238
0 (Sunday)
41AC
Daylight Savings Time (DST) Start Day Instance
0 to 4
---
1
F239
0 (First)
Table B–9: MODBUS MEMORY MAP (Sheet 21 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание M60 UR Series
Страница 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Страница 98: ...3 40 M60 Motor Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 238: ...5 110 M60 Motor Protection System GE Multilin 5 4 SYSTEM SETUP 5 SETTINGS 5 Figure 5 29 DISCONNECT SWITCH SCHEME LOGIC ...
Страница 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 413: ...GE Multilin M60 Motor Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 29 ...
Страница 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Страница 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Страница 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 662: ...x M60 Motor Protection System GE Multilin INDEX ...