B-38
M60 Motor Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Motor Setup (Read/Write Setting)
6600
Thermal Model Motor FLA
0.05 to 1
pu
0.001
F001
1000
6601
Thermal Model Motor Overload Factor
1 to 1.5
---
0.01
F001
100
6602
Thermal Model Line Source
0 to 5
---
1
F167
0 (SRC 1)
6603
Thermal Model Motor Offline
0 to 4294967295
---
1
F300
0
6605
Thermal Model RTD 1
0 to 48
---
1
F151
0 (NONE)
6606
Thermal Model RTD 2
0 to 48
---
1
F151
0 (NONE)
6607
Thermal Model RTD 3
0 to 48
---
1
F151
0 (NONE)
6608
Thermal Model RTD 4
0 to 48
---
1
F151
0 (NONE)
6609
Thermal Model RTD 5
0 to 48
---
1
F151
0 (NONE)
660A
Thermal Model RTD 6
0 to 48
---
1
F151
0 (NONE)
660B
Motor Emergency Restart
0 to 4294967295
---
1
F300
0
660D
Motor Nameplate Voltage
100 to 50000
V
1
F001
600
660E
Speed 2 Motor Protection
0 to 1
---
1
F102
0 (Disabled)
660F
Speed 2 Motor Switch
0 to 4294967295
---
1
F300
0
6611
Speed 2 Switch 2-1 Delay
0 to 600
s
0.01
F001
500
6612
Speed 2 Motor Source
0 to 5
---
1
F167
0 (SRC 1)
6613
Speed 2 Motor FLA
0.05 to 1
pu
0.001
F001
1000
Thermal Model Actuals (Read Only)
6630
Thermal Model Motor Status
0 to 3
---
1
F098
1 (Starting)
6631
Thermal Model Capacity Used
0 to 100
%
1
F001
0
6633
Trip Time On Overload
0 to 10000
---
1
F001
0
6634
Thermal Model Lockout Time
0 to 65000
min
1
F001
0
6638
Thermal Model Load
0 to 40
x FLA
0.01
F001
0
663A
Thermal Model Motor Unbalance
0 to 100
%
1
F001
0
663B
Thermal Model Biased Motor Load
0 to 40
x FLA
0.01
F001
0
663C
Start/Hour Lockout Time
0 to 65000
min
1
F001
0
663D
Time-Between-Starts Lockout Time
0 to 65000
min
1
F001
0
663E
Restart Delay Lockout Time
0 to 50000
s
1
F001
0
663F
Total Motor Lockout Time
0 to 65000
min
1
F001
0
Sensitive Directional Power (Read/Write Grouped Setting) (2 Modules)
6680
Sensitive Directional Power 1 Function
0 to 1
---
1
F102
0 (Disabled)
6681
Sensitive Directional Power 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
6682
Sensitive Directional Power 1 RCA
0 to 359
degrees
1
F001
0
6683
Sensitive Directional Power 1 Calibration
0 to 0.95
degrees
0.05
F001
0
6684
Sensitive Directional Power 1 STG1 SMIN
-1.2 to 1.2
pu
0.001
F002
100
6685
Sensitive Directional Power 1 STG1 Delay
0 to 600
s
0.01
F001
50
6686
Sensitive Directional Power 1 STG2 SMIN
-1.2 to 1.2
pu
0.001
F002
100
6687
Sensitive Directional Power 1 STG2 Delay
0 to 600
s
0.01
F001
2000
6688
Sensitive Directional Power 1 Block
0 to 4294967295
---
---
F300
0
668A
Sensitive Directional Power 1 Target
0 to 2
---
1
F109
0 (Self-reset)
668B
Sensitive Directional Power 1 Events
0 to 1
---
1
F102
0 (Disabled)
668C
Reserved (5 items)
0 to 65535
---
1
F001
0
6691
...Repeated for Sensitive Directional Power 2
Underpower (Read/Write Grouped Setting) (2 Modules)
66AA
Underpower 1 Function
0 to 1
---
1
F102
0 (Disabled)
66AB
Underpower 1 Start Block Delay
0 to 600
s
0.01
F001
50
66AC
Underpower 1 Alarm Power Pickup
0.05 to 2
pu
0.01
F001
50
66AD
Underpower 1 Alarm Pickup Delay
0 to 600
s
0.01
F001
200
66AE
Underpower 1 Trip Power Pickup
0.05 to 2
pu
0.01
F001
40
66AF
Underpower 1 Trip Pickup Delay
0 to 600
s
0.01
F001
100
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 66)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание M60 UR Series
Страница 10: ...x M60 Motor Protection System GE Multilin TABLE OF CONTENTS ...
Страница 98: ...3 40 M60 Motor Protection System GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 128: ...4 30 M60 Motor Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 238: ...5 110 M60 Motor Protection System GE Multilin 5 4 SYSTEM SETUP 5 SETTINGS 5 Figure 5 29 DISCONNECT SWITCH SCHEME LOGIC ...
Страница 410: ...5 282 M60 Motor Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 413: ...GE Multilin M60 Motor Protection System 6 3 6 ACTUAL VALUES 6 1 OVERVIEW 6 FIRMWARE REVISIONS See page 6 29 ...
Страница 440: ...6 30 M60 Motor Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 452: ...7 12 M60 Motor Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 462: ...9 8 M60 Motor Protection System GE Multilin 9 2 BATTERIES 9 MAINTENANCE 9 ...
Страница 474: ...A 12 M60 Motor Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 584: ...B 110 M60 Motor Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 614: ...C 30 M60 Motor Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 630: ...E 10 M60 Motor Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 642: ...F 12 M60 Motor Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 644: ...G 2 M60 Motor Protection System GE Multilin G 1 RADIUS SERVER CONFIGURATION APPENDIX G G ...
Страница 652: ...H 8 M60 Motor Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Страница 662: ...x M60 Motor Protection System GE Multilin INDEX ...