iBox/iBox Kit
Installation and Maintenance Guide
GE Grid Solutions
28
994-0047-5.10-4
GE Information
Installation Guidelines
Installation
Environment
The iBox must be installed in an environment that provides protection against shock
and fire hazard.
The iBox enclosure is intended for indoor use, primarily to provide protection
against accidental contact with the enclosed modules and voltages. Do not place the
product in environments where unusual conditions exist (windblown dust and dirt,
for example) unless you install it in a secondary protective enclosure.
Never operate an iBox in the field with the top cover removed. Operation with the
top cover removed may alter product performance specifications, and result in
component damage from foreign matter entry.
Do not install and/or operate the iBox upside down.
Ensure all nuts and screws are tightened securely.
Ensure that iBox is protected from falling debris during installation.
Power Supply
Source
An IEC
®
60947 compliant main disconnect switch (or other equivalent device
complying with IEC 60947-1 / 60947-3) must be as electrically close as practicable
to the iBox power supply.
For correct iBox power supply operation, the input voltage must be within specified
limits.
The iBox DC power supply draws an inrush current (less than 0.5 A) upon start-up.
Ensure the field source can supply this start-up current without overloading.
Continued on next page
Содержание iBox
Страница 142: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 142 994 0047 5 10 4 GE Information ...
Страница 154: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 154 994 0047 5 10 4 GE Information ...
Страница 156: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 156 994 0047 5 10 4 GE Information ...
Страница 162: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 162 994 0047 5 10 4 GE Information ...
Страница 172: ......