GE Grid Solutions
iBox/iBox Kit
Installation and Maintenance Guide
GE Information
994-0047-5.10-4
147
Technical Specifications – iBox Kit
, continued
Digital Inputs
General
Up to eight bipolar optically isolated (2000 V
rms
)
Physical
250 V
rated compression termination consisting of a
header and removable plugs suitable for 12 – 24 AWG
wire 0.01A/150V
Burden
•
From 1.9 mA to 5.5 mA
•
Max. power dissipation is 0.5 W per input
Wetting Options
•
External wetting - for all input options
•
Modes of operation:
−
Dry contact and voltage sense
−
24 VDC, 48 VDC, and 110/125 VDC
Digital
Outputs
General
Up to four relay outputs, configured as either:
•
4 trip/close pairs or
•
2 trip/close pairs and 2 Form A contacts
Physical Connection
250 V rated compression termination consisting of a
header and removable plugs suitable for 12 – 24 AWG
wire rated for 6A/150V
Security features
•
Separate Master Trip and Master Close relays
•
Single point of failure integrity, select-before-operate
(SBO) functionality.
•
Remote/Local jumper JP2
Control Voltage
External
Switching Characteristics
•
35 W breaking @ 150 VDC
•
180 W breaking @ 30 VDC
Maximum Carrying
Current
6 A
Continued on next page
Содержание iBox
Страница 142: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 142 994 0047 5 10 4 GE Information ...
Страница 154: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 154 994 0047 5 10 4 GE Information ...
Страница 156: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 156 994 0047 5 10 4 GE Information ...
Страница 162: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 162 994 0047 5 10 4 GE Information ...
Страница 172: ......