GE Grid Solutions
iBox/iBox Kit
Installation and Maintenance Guide
GE Information
994-0047-5.10-4
103
Configuring the iBox PPP Driver and Internet Data Links
Procedure:
Configuring
the PPP
Driver
Step
Action
1
Select the iBox device.
2
Click
Communications
>
Options
.
Result: The D2x Device Communication Options window > Interface tab
appears.
3
Select the
PPP
Connection Type.
Result: The tabs applicable to the connection type appear.
4
Click the
Tables
tab.
5
On the
PPP main config
tab, verify the following settings and modify
them if necessary:
Field
Value
Port
COM3
Baud
19.2K
Bits per char
8
Parity Type
Even
Parity Mode
None
Stop Bits
1
RTS
Disable
CTS
Disable
DCD
Enable
RTS on delay
0
DCD on delay
0
RTS off delay
0
Max PPP receive unit
1500
Restart timer
3
ACCM
Disable
CHAP
Disable
Challenge_retries
2
Challenge_period
5
Note:
You should not need to change any of the above settings from
their default values. If you do, you also need to make
corresponding changes to the Digi One
®
Ethernet Module, if
equipped, or to the equipment to which the iBox Ethernet port is
connected. See “Configuring the Ethernet Module” on page 109.
6
Close the
PPP Driver
window.
7
Click
Yes
to save your changes.
Continued on next page
Содержание iBox
Страница 142: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 142 994 0047 5 10 4 GE Information ...
Страница 154: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 154 994 0047 5 10 4 GE Information ...
Страница 156: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 156 994 0047 5 10 4 GE Information ...
Страница 162: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 162 994 0047 5 10 4 GE Information ...
Страница 172: ......