iBox/iBox Kit
Installation and Maintenance Guide
GE Grid Solutions
128
994-0047-5.10-4
GE Information
Configuring the DC Analog Module
, continued
Procedure:
Configuring
the ADAM-
4017+
(continued)
Step
Action
12
Click
Update
, then
OK
when you receive the message that the setup was
successful:
13
Remove power to the ADAM-4017+.
14
Change the ADAM-4017+ operating mode switch from
Init
back to
Normal
.
15
Restore power to the ADAM-4017+.
16
In the ADAM-4000 Utility, click .
Result:
The device configuration is now consistent with the change or
changes you made.
17
Remove power to the ADAM-4017+.
18
Disconnect the ADAM-4017+ from the RS-485/RS-232 converter, and
reconnect it to the iBox.
Procedure:
Modifying the
Point
Descriptors
You may wish to modify the default point descriptions for the DC Analog Inputs to
more meaningful descriptions for your system. Follow these steps to change the
point descriptors of the DC analog inputs.
Step
Action
1
Open the iBox Kit device in SGConfig, open the
Applications List
, and
click the
System Point Database Applications
tab.
2
Double-click the
System Point Database
icon.
Result:
The
System Point Database Properties
window displays.
3
On the
DCA/DTA List
tab, select
MODBUS DCA
and click the
Descriptors
button.
Result:
The
Point Descriptors
window appears.
4
Click the
Analog Inputs
tab on the bottom of the window. Enter new
Point Descriptions
as desired. Click
OK
.
5
On the
DCA/DTA List
tab, select
Calculator DTA
and click the
Descriptors
button.
Result:
The
Point Descriptors
window appears.
6
Click the
Analog Inputs
tab on the bottom of the window. Enter new
Point Descriptions
as desired. Click
OK
twice.
Result:
SGConfig updates the configuration tables.
Содержание iBox
Страница 142: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 142 994 0047 5 10 4 GE Information ...
Страница 154: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 154 994 0047 5 10 4 GE Information ...
Страница 156: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 156 994 0047 5 10 4 GE Information ...
Страница 162: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 162 994 0047 5 10 4 GE Information ...
Страница 172: ......