GE Grid Solutions
iBox/iBox Kit
Installation and Maintenance Guide
GE Information
994-0047-5.10-4
71
Runtime and Startup Errors
, continued
iBox Trouble-
shooting Tips
Symptom
Possible Causes
Suggestions
Active Operations
Aborted
Controls Jumper is in the Local
position (JP2 is removed).
Move the Controls Jumper
to the Remote position
(Install JP2).
Active Requests
Aborted
The iBox Plant I/O Subsystem
monitoring detects a conflict
between desired and actual
coil status (a coil is not
energized when it should be).
Verify coil status.
Digital Output
Requests Rejected
Controls Jumper is in the Local
position (JP2 is removed).
The iBox Plant I/O Subsystem
monitoring detects a conflict
between desired and actual
coil status (a coil is not
energized when it should be).
Move the Controls Jumper
to the Remote position
(Install JP2).
Verify coil status.
Queued Requests
Cleared
Controls Jumper is in the Local
position.
The iBox Plant I/O Subsystem
monitoring detects a conflict
between desired and actual
coil status (a coil is not
energized when it should be).
Move the Controls Jumper
to the Remote position
Verify coil status
System Hangs
Watchdog failure.
Attempt Reboot, clear CCU
error logs
Plant I/O Watchdog
Failure
Plant I/O Subsystem integrity is
faulty.
Remove and restore power
to the iBox
Digital output Points
are Disabled
The Local/Remote Jumper is in
the Local position (JP2 is
removed).
Move the Local/Remote
Jumper to the Remote
position (Install JP2).
Communication
Watch Dog Failure
Internal system monitors
detect serious errors.
Attempt Reboot, clear CCU
error logs.
Coil Status Check
The iBox Plant I/O Subsystem
monitoring detects a conflict
between desired and actual
coil status.
Verify coil status.
Digital output coils are
not in the state
requested by the
software
Plant I/O Sub failure
Hardware Watchdog.
Check Control Voltage
source fuses. Check voltage.
Force from WESMAINT
Digital Output Failure
Control Voltage Not Available,
Coil Status Check, or Hardware
Watchdog error condition.
Check Control Voltage
source fuses. Check voltage.
Force from WESMAINT.
Continued on next page
Содержание iBox
Страница 142: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 142 994 0047 5 10 4 GE Information ...
Страница 154: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 154 994 0047 5 10 4 GE Information ...
Страница 156: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 156 994 0047 5 10 4 GE Information ...
Страница 162: ...iBox iBox Kit Installation and Maintenance Guide GE Grid Solutions 162 994 0047 5 10 4 GE Information ...
Страница 172: ......