Placement of Standby Generator to REDUCE THE RISK OF FIRE
The National Fire Protection Association (NFPA) standard
NFPA 37 establishes criteria for minimizing the hazard
of fire during the installation and operation of stationary
combustion engines. NFPA 37 limits the spacing of an
enclosed generator from openings in walls, structures and
combustible materials outside the enclosure.
The placement requirements provided are based on
compliance to NFPA 37 2010 section 4.1.4.
WARNING
Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5 m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 feet (1.5 m) overhead clearance from any structure, overhang
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• DO NOT place weatherproof enclosure in manner other than
shown in illustrations.
Examples of standby generator locations to reduce the
risk of fire:
Legend for Generator Locations to reduce the risk of fire.
A
Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
C
Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE
DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
Vertical Clearances
A
A
A
A
C
NOT
for
REPRODUCTION
Содержание 60000 Series
Страница 28: ...28 Schematic Diagram Page 29 Page 31 Page 33 Page 30 Page 32 Page 34 N O T f o r R E P R O D U C T I O N...
Страница 31: ...31 Schematic Diagram continued YEL 18 BLK 18 GRY 20 YEL 18 BLK 14 N O T f o r R E P R O D U C T I O N...
Страница 33: ...33 Schematic Diagram continued GRY 20 YEL 18 GRN 20 YEL 20 BLK 14 N O T f o r R E P R O D U C T I O N...
Страница 35: ...35 N O T f o r R E P R O D U C T I O N...
Страница 36: ...36 Wiring Diagram ComAp InteliNano Control Panel N O T f o r R E P R O D U C T I O N...
Страница 37: ...37 Wiring Diagram ComAp InteliNano Control Panel N O T f o r R E P R O D U C T I O N...
Страница 38: ...38 Wiring Diagram ComAp InteliLite Control Panel N O T f o r R E P R O D U C T I O N...
Страница 39: ...39 Wiring Diagram ComAp InteliLite Control Panel N O T f o r R E P R O D U C T I O N...