A–48
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
TICS
TICS
This section contains the TISSUES (Technical Issues) Implementation Conformance
Statement (TICS) for the IEC 61850 interface in the 3 Series Family of protective relays.
Date: January 3, 2017
Version 1.10
1 Introduction
This tissues conformance statement is applicable to the 3 Series family with firmware
version 2.30.
2 Implemented IntOp TISSUES
During the October 2006 meeting IEC TC57 working group 10 decided that:
•
green Tissues with the category "IntOp" are mandatory for IEC 61850 edition 1
•
Tissues with the category "Ed.2" Tissues should not be implemented.
Mandatory Edition 1 Tissues
The following table gives an overview of the implemented mandatory Tissues.
Part
Tissue
Nr
Description
Implemented
Y/na
8-1
116
GetNameList with empty response?
Y
165
Improper Error Response for GetDataSetValues
Y
183
GetNameList error handling
Y
226
Control negative response (SBOns) with LastApplError
na
545
Skip file directories with no files
na
7-4
252
AlmThm should have CDC SPS
na
7-3
28
Definition of APC
na
54
Point def xVal, not cVal
na
55
Ineut = Ires ?
Y
63
mag in CDC CMV
Y
65
Deadband calculation of a Vector and trigger option
Y
219
operTm in ACT
na
270
WYE and DEL rms values
na
1199
BCR
na
7-2
30
control parameter T
na
31
Typo
na
32
Typo in syntax
na
35
Typo Syntax Control time
na
36
Syntax parameter DSet-Ref missing
na
37
Syntax GOOSE "T" type
Y
39
Add DstAddr to GoCB
Y
40
GOOSE Message "AppID" to "GoID
"Y
41
GsCB "AppID" to "GsID
"na
42
SV timestamp: "EntryTime" to "TimeStamp
"na