CHAPTER 5: 350 OPC–UA COMMUNICATION STANDARD
OPC–UA POINT LISTS
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
5-3
OPC–UA Point Lists
•
Modeling for the following:
Events
All digital signals available are defined as an event source. So, the Server connection is
declared as a unique event notifier.
Alarms
The alarms are not supported.
Commands
The Open&Close breaker and Reset commands have been implemented as Method
services.
•
The OPC-UA server has implemented the following Analog, Digital, Input, Logic and
Command points, as shown in the tables.
Table 5-1: Analog points
Data
Description
W
Real Power
VAr
Reactive Power
VA
Apparent Power
PF
Power Factor
Freq
Frequency
Vab
PhA to PhB Voltage
Vab_ang
Va angle
Vbc
PhB to Ph CVoltage
Vbc_ang
Vb angle
Vca
PhCtoPhAVoltage
Vca_ang
Vc angle
Va_mag
Va magnitude
Va_ang
Va angle
Vb_mag
Vb magnitude
Vb_ang
Vb angle
Vc_mag
Vc magnitude
Vc_ang
V cangle
Vn_mag
Vn magnitude
Vn_ang
Vn angle
Ia_mag
Ia magnitude
Ia_ang
Ia angle
Ib_mag
Ib magnitude
Ib_ang
Ib angle
Ic_mag
Ic magnitude
Ic_ang
Ic angle
Ig_mag
Ground magnitude
Ig_ang
Ground angle
In_mag
Neutral magnitude
In_ang
Neutral angle
Is_mag
Sensitive Ground magnitude
Is_ang
Sensitive Ground angle
Vaux_mag
Auxiliary Voltage magnitude