A–56
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PICS
S24
1,2 Report
TP
Y
S24-1
1,2
data-
change
(dchg)
Y
S24-2
1,2
quality-
change
(qchg)
N
S24-3
1,2
data-update
(dupd)
N
S25
1,2 GetBRCBValues
TP
Y
S26
1,2 SetBRCBValues
TP
Y
Unbuffered report control block (URCB)
S27
1,2 Report
TP
Y
S27-1
1,2
data-
change
(dchg)
Y
S27-2
1,2
quality-
change
(qchg)
N
S27-3
1,2
data-update
(dupd)
N
S28
1,2 GetURCBValues
TP
Y
S29
1,2 SetURCBValues
TP
Y
Logging
Log control
S30
1,2 GetLCBValues
TP
N
S31
1,2 SetLCBValues
TP
N
Log
S32
1,2 QueryLogByTime
TP
N
S33
1,2 QueryLogAfter
TP
N
S34
1,2 GetLogStatusValues
TP
N
Generic substation event model (GSE)
GOOSE
S35
1,2 SendGOOSEMessage
MC
Y
GOOSE Control Block
S36
1,2 GetGoReference
TP
S37
1,2 GetGOOSEElementNumber
TP
S38
1,2 GetGoCBValues
TP
Y
S39
1,2 SetGoCBValues
TP
Y
GSSE (Ed2:61850-7-2 Annex C)
S40
1,2 SendGSSEMessage
MC
N
Deprecated in Edition 2
GSSE Control
Block (Ed2:61850-7-2 Annex C)
S41
1,2 GetGsReference
TP
N
Deprecated in Edition 2
S42
1,2 GetGSSEDataOffset
TP
N
Deprecated in Edition 2
S43
1,2 GetGsCBValues
TP
N
Deprecated in Edition 2
S44
1,2 SetGsCBValues
TP
N
Deprecated in Edition 2
Ed
ACSI Service
AA:
TP/MC
Client Sub
(C)
Server Pub
(S)
Comments
Содержание 339
Страница 4: ...1 iv SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE COMMUNICATIONS INTERFACES CHAPTER 1 INTRODUCTION ...
Страница 164: ...8 16 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ERROR RESPONSES CHAPTER 8 MODBUS FUNCTIONS ...