A–64
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PIXIT
PIXIT for Control model
ID
Ed
Description
Value / Clarification
Ct1
-
What control models are supported
(compare PICS)
Deprecated
Ct2
1,2
Is the control model fixed, configurable and/or dynamic
Configurable & Dynamic
Ct3
-
Is TimeActivatedOperate supported (compare PICS or SCL)
Deprecated
Ct4
1,2
Is "operate-many" supported (compare sboClass)
Deprecated
Ct5
1
Will the DUT activate the control output when the test attribute is set in
the SelectWithValue and/or Operate request (when N test procedure Ctl2
is applicable)
N
Ct6
-
What are the conditions for the time (T) attribute in the SelectWithValue
and/or Operate request
Deprecated
Ct7
-
Is pulse configuration supported (compare pulseConfig)
Deprecated
Ct8
1
What is the behaviour of the DUT when the check conditions are set
Is this behaviour fixed, configurable, online changeable
N synchrocheck
N interlock-check
DUT ignores the check value and always
perform the check
Ct9
1,2
Which additional cause diagnosis are supported
Y Unknown
Y Not-supported
Y Blocked-by-switching-hierarchy
Y Select-failed
Y Invalid-position
Y Position-reached
N Step-limit
N Blocked-by-Mode
N Blocked-by-process
N Blocked-by-interlocking
N Blocked-by-synchrocheck
Y Command-already-in-execution
N Blocked-by-health
N 1-of-n-control
N Abortion-by-cancel
Y Time-limit-over
N Abortion-by-trip
Y Object-not-selected
Edition 1 specific values:
N Parameter-change-in-execution
Edition 2 specific values:
N Object-already-selected
N No-access-authority
N Ended-with-overshoot
N Abortion-due-to-deviation
N Abortion-by-communication-loss
N Blocked-by-command
N None
N Inconsistent-parameters
N Locked-by-other-client
N Parameter-change-in-
execution
Ct10
1,2
How to force a "test-not-ok" respond with SelectWithValue request
Device in local mode
Ct11
1,2
How to force a "test-not-ok" respond with Select request
Device in local mode
Ct12
1,2
How to force a "test-not-ok" respond with Operate request
DOns: Sending T=1
SBOns: Sending T=1
DOes:
Sending T=1
SBOes: Sending T=1
Ct13
1,2
Which origin categories are supported / accepted
N bay-control
Y station-control
Y remote-control
N automatic-bay
Y automatic-station
Y automatic-remote
N maintenance
N process
Содержание 339
Страница 4: ...1 iv SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE COMMUNICATIONS INTERFACES CHAPTER 1 INTRODUCTION ...
Страница 164: ...8 16 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ERROR RESPONSES CHAPTER 8 MODBUS FUNCTIONS ...