CHAPTER 4: 3 SERIES IEC61850 GOOSE
USING THE IEC 61850 CONFIGURATOR
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
4-33
Configuration lab
steps
1.
Configure both relays in the EnerVista 3 Series Setup software and set the GOOSE
transmission of both relays to Advanced.
Configure both 3 Series relays into the EnerVista 3 Series Setup application using the
following procedure
1.1.
Launch the EnerVista 3 Series Setup software and select
Device Setup.
1.2.
Select
Add Site.
1.3.
Enter an optional site name.
1.4.
Select
Add Device.