3-18
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
DNP ETHERNET PROTOCOL SETTINGS
CHAPTER 3: ETHERNET INTERFACE
NOTE
NOTE:
The setting
DNP Unsolicited Response Timeout
affects DNP TCP clients only; not serial
and UDP clients. Possible values that can be selected for this setting lie between 0 and 60
seconds.
In addition to this selected timeout, up to an additional 10 seconds is required to send
the response packet.
Table 3-2: DNP point list
•
The DNP Time Sync IIN Period setting determines how often the Need Time Internal
Indication (IIN) bit is set by the 3 Series relay. Changing this time allows the 3 Series
relay to indicate that a time synchroniztion command is necessary more or less often
DNP Object 1 Default Variation
2
1 ; 2
F1
DNP Object 2 Default Variation
2
1 ; 2
F1
DNP Object 20 Default Variation
1
1 ; 2 , 5 ; 6
F78
DNP Object 21 Default Variation
1
1 ; 2 ; 9 ; 10
F79
DNP Object 22 Default Variation
1
1 ; 2 , 5 ; 6
F80
DNP Object 23 Default Variation
1
1 ; 2 , 5 ; 6
F81
DNP Object 30 Default Variation
1
1 ; 2 ;3 ; 4
F82
DNP Object 32 Default Variation
1
1 ; 2 ;3 ; 4
F83
DNP TCP Connection Timeout
120 s
10 to 300 s
F1
Fault Report Mapping in DNP/104 Disabled
Disabled, Enabled
F126
SETTINGS
PARAMETER
RANGE
FORMAT
SETTINGS
PARAMETER
RANGE
FORMAT
Binary Input Point 0 Entry
Select entry
from a list
Operands
FC134B
Binary Input Point 63 Entry
Select entry
from a list
Operands
FC134B
Analog Input Point 0 Entry
Select entry
from a list
Analog parameters
F88
Analog Input Point 0 Scale Factor 1
0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ;
1000 ; 10000 ; 100000
F85
Analog Input Point 0 Deadband
30000
0 to 100000000
F9
Analog Input Point 31 Entry
Select entry
from a list
Analog parameters
F88
Analog Input Point 31 Scale Factor 1
0.001 ; 0.01 ; 0.1 ; 1 ; 10 ; 100 ;
1000 ; 10000 ; 100000
F85
Analog Input Point 31 Deadband
30000
0 to 100000000
F9
Binary Output Point 0 ON
Select entry
from a list
Virtual Input 1 to 32 and Force
Coils
F86
Binary Output Point 0 OFF
Select entry
from a list
Virtual Input 1 to 32 and Force
Coils
F86
Binary Output Point 15 ON
Select entry
from a list
Virtual Input 1 to 32 and Force
Coils
F86
Binary Output Point 15 OFF
Select entry
from a list
Virtual Input 1 to 32 and Force
Coils
F86
Содержание 339