A–58
3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
PIXIT
PIXIT
This section contains the Protocol Implementation eXtra Information for Testing (PIXIT) for
the IEC 61850 interface in the 3 Series Family of protective relays.
Version 1.10
Date: January 3, 2017
Introduction
This document specifies the protocol implementation extra information for testing (PIXIT)
of the IEC 61850 interface in the 3 Series Family with firmware version 2.30
Together with the PICS and the MICS, the PIXIT forms the basis for a conformance test
according to IEC 61850-10. The PIXIT entries contain information which is not available in
the PICS, MICS, TICS documents or SCL file.
Each table specifies the PIXIT for applicable ACSI service model as structured in IEC 61850-
10. The "Ed" column indicates if the entry is applicable for IEC 61850 Edition 1 and/or
Edition 2.
PIXIT for Association model
ID
Ed
Description
Value / Clarification
As1
1
Maximum number of clients that can set-up an
association simultaneously
3
As2
1,2
TCP_KEEPALIVE value. The recommended range is
1..20s
20 seconds but if no application message is
detected within the As3 value, the device will
close the connection.
As3
1,2
Lost connection detection time
120 seconds (Configurable)
As4
-
Authentication is not supported yet
As5
1,2
What association parameters are necessary for
successful association
Transport selector
Session selector
Presentation selector
AP Title
AE Qualifier
Y
Y
Y
N
N
As6
1,2
If association parameters are necessary for
association, describe the correct values e.g.
Transport selector
Session selector
Presentation selector
AP Title
AE Qualifier
0001
0001
00000001
NA
NA
As7
1,2
What is the maximum and minimum MMS PDU size
Max MMS PDU size
Min MMS PDU size
120000
700.
As8
1,2
What is the maximum start up time after a power
supply interrupt
45-50 seconds.
(90 seconds in the worst case when creating
default.cid)
Содержание 339
Страница 4: ...1 iv SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE COMMUNICATIONS INTERFACES CHAPTER 1 INTRODUCTION ...
Страница 164: ...8 16 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ERROR RESPONSES CHAPTER 8 MODBUS FUNCTIONS ...