CHAPTER 2: RS485 INTERFACE
IEC 60870-5-103 SERIAL COMMUNICATION
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
2-23
Data management
The 3 Series relay supports a fixed profile and data that is configurable using the EnerVista
3 Series Setup program.
The data that can be configured are:
•
digital states
•
measurands
•
commands.
Digital states
Digital states in the relay may be mapped using the EnerVista 3 Series Setup program. By
default, states are mapped to information numbers proposed by the standard, but the
user may delete these mappings if desired.
All the mapped information will be sent as a response to a general interrogation like ASDU
1.
For the other states, the customer can assign:
1.
Information Number <1..255>
2.
Function Type <0..255>.
This means that for each digital point 3 settings are required.
Example
:
The “Point Entry Digital Status” reuses the DNP Binary Input 43029, 43030, …
Measurands
Some analog points are supported by the 3 Series relay with compatible information
numbers that have been identified in the device profile.
For the other measurands, it is possible to use the EnerVista 3 Series Setup to select the
desired point and assign the Identification Type (3 or 9), Function Type <0..255>, and
Information Number <1..255>.
If the user selects Identification Type 3 (ASDU 3) only four measurands are available for
configuration, but if Identification Type 9 (ASDU 9) is selected, up to nine measurands can
be sent in the IEC103 slave answer. For each measurand, all metering values that the 3
Series relay supports, are available in order to be mapped. There are 3 possible
configurable ASDUS.
For example, eDataVab is the index in the Modbus Memory Map.
Settings
Digital Status
Information Number
Function Type
Point 1 Entry
Select entry from list
<0 – 255 >
<0 – 255 >
….
.…
Point 64 Entry
Select entry from list
<0 – 255 >
<0 – 255 >
Modbus Address
Description
Value
Format
43879
Point 1 Entry Digital Status
0x8242 (Undercurrent Trip)
FC134
44223
Point 1 Entry Function Type
160
F1
44224
Point 1 Entry Information Number
144
F1
Modbus Address
Description
Value
Format
44384
First ASDU Identification Type
3 or 9
F221
44385
First ASDU Function Type
<0 - 255 >
F1
44386
First ASDU Information Number
< 0 - 255 >
F1
44387
First ASDU Scan Timeout
< 0 - 1000> secs
F1