10-32
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
339 MODBUS MEMORY MAP
CHAPTER 10: 339 MODBUS MEMORY MAP AND FORMAT CODES
41241
0x4D8
Logic Element 16 Asserted
0
1
1
---
FC103
0
1
41242
0x4D9
Logic Element 16 Relay
0
0x7F
1
---
FC198
0
1
CONTACT INPUT ASSIGNMENT
41374
0x55D
Lockout Reset
0
0xEF02
1
---
F89A
0
1
41380
0x563
Remote Reset
0
0xEF02
1
---
F89A
0
1
41386
0x569
Remote Open
0
0xEF02
0
---
F89A
0
1
41387
0x56A
Remote Close
0
0xEF02
0
---
F89A
0
1
41389
0x56C
Breaker 52a Contact
0
0x40
0
---
FC204A
0
1
41390
0x56D
Breaker 52b Contact
0
0x41
0
---
FC204C
0
1
41391
0x56E
Local Mode
0
0xEF02
0
---
F89
0
1
41406
0x57D
High Speed Switch
0
0xEF02
1
---
F89
0
1
41407
0x57E
Low Speed Switch
0
0xEF02
1
---
F89
0
1
41408
0x57F
Emergency Restart
0
0xEF02
1
---
F89A
0
1
CONTACT INPUT NAMES (9 TO 10)
41435
0x59A
Input Name 9
0
7
1
---
F22
Input 9
7
41444
0x5A3
Input Name 10
0
7
1
---
F22
Input 10
7
CONTACT INPUTS
41454
0x5AD
Input 9 Debounce Interval
1
64
1
ms
F1
2
1
41455
0x5AE
Input 10 Debounce Interval 1
64
1
ms
F1
2
1
41456
0x5AF
Input 1 Debounce Interval
1
64
1
ms
F1
2
1
41457
0x5B0
Input 2 Debounce Interval
1
64
1
ms
F1
2
1
41458
0x5B1
Input 3 Debounce Interval
1
64
1
ms
F1
2
1
41459
0x5B2
Input 4 Debounce Interval
1
64
1
ms
F1
2
1
41460
0x5B3
Input 5 Debounce Interval
1
64
1
ms
F1
2
1
41461
0x5B4
Input 6 Debounce Interval
1
64
1
ms
F1
2
1
41462
0x5B5
Input 7 Debounce Interval
1
64
1
ms
F1
2
1
41463
0x5B6
Input 8 Debounce Interval
1
64
1
ms
F1
2
1
41465
0x5B8
Select DC Voltage
0
3
1
---
FC123
2
1
FRONT PANEL SETUP
41475
0x5C2
Screen Saver
0
10000
1
min
F1C
0
1
41498
0x5D9
Stopped LED Colour
0
3
1
---
FC157
1
1
41500
0x5DB
Starting LED Colour
0
3
1
---
FC157
3
1
41502
0x5DD
Running LED Colour
0
3
1
---
FC157
2
1
OUTPUT RELAYS
41509
0x5E4
Close Relay Type
0
1
1
---
FC199
0
1
41510
0x5E5
Relay 3 Type
0
1
1
---
FC199
0
1
41511
0x5E6
Relay 4 Type
0
1
1
---
FC199
0
1
41512
0x5E7
Relay 5 Type
0
1
1
---
FC199
0
1
41513
0x5E8
Relay 6 Type
0
1
1
---
FC199
0
1
OUTPUT RELAY BLOCKING
41547
0x60A
Block Relay 1 Trip
0
0xEF02
1
---
F89
0
1
41548
0x60B
Block Relay 2 Close
0
0xEF02
1
---
F89
0
1
OUTPUT RELAY OPERATION
41552
0x60F
Relay 1 Operation
0
1
1
---
FC208
1
1
41553
0x610
Relay 2 Operation
0
1
1
---
FC208
1
1
41554
0x611
Relay 3 Operation
0
1
1
---
FC208
1
1
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
words
Содержание 339
Страница 4: ...1 iv SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ...
Страница 10: ...1 2 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE COMMUNICATIONS INTERFACES CHAPTER 1 INTRODUCTION ...
Страница 164: ...8 16 SR3 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE ERROR RESPONSES CHAPTER 8 MODBUS FUNCTIONS ...